beautypg.com

1off – Bryant 355MAV EN User Manual

Page 35

background image

1. Remove main furnace door and blower access panel.

2. Locate CF setup switches on control center. (See Fig. 25.)

3. Determine desired continuous fan airflow.

4. Use Table 9 or wiring schematic to determine proper setup

position of CF switches. (See Fig. 24 and 45.)

NOTE:

The CF switches are factory set to provide continuous fan

airflow equal to low-heat mode.

5. Replace main furnace door and blower access panel.

C.

Setup Switches (SW)

The control center has 8 setup switches that may be set to meet the
application requirements. Position these setup switches for the
appropriate requirement.

1. Remove main furnace door and blower access panel.

2. Locate setup switches on control center. (See Fig. 25.)

3. See Table 10 for setup switch description. (See Fig. 24 and

45.)

4. Replace main furnace door and blower access panel.

NOTE:

If a bypass humidifier is used, setup switch SW-3 (BPH)

should be in ON position. This prevents nuisance limit trips caused
by the increased temperature in return air resulting from bypass.

NOTE:

If modulating dampers are used, setup switch SW-5 (MZ)

should be in ON position. This allows furnace control center to
compensate for modulating dampers. The control re-calibrates for
new system static conditions once every minute while operating in
low-heat or continuous fan modes.

III.

PRIME CONDENSATE TRAP WITH WATER

CAUTION:

Condensate trap must be PRIMED or

proper draining may not occur. The condensate trap has 2
internal chambers which can ONLY be primed by pour-
ing water into the inducer drain side of condensate trap.

1. Remove upper inducer housing drain connection cap. (See

Fig. 46.)

2. Connect field-supplied 1/2-in. ID tube to upper inducer

housing drain connection.

3. Insert field-supplied funnel into tube.

4. Pour 1 quart of water into funnel/tube. Water should run

through inducer housing, overfill condensate trap, and flow
into open field drain. (See Fig. 47.)

5. Remove funnel and tube from inducer housing and replace

drain connection cap and clamp.

TABLE 8—AIR CONDITIONING (A/C) AIRFLOW SETUP SWITCH POSITION

AIR

CONDITIONER

(TONS)

CFM AIRFLOW

A/C SETUP

SWITCH POSITION

ALLOWABLE FURNACE MODEL SETUP

A/C-1

A/C-2

A/C-3

042040

042060

042080

060080

060100

060120

Default

1200 or

2000

OFF

OFF

OFF

3 Tons

1200 CFM

3 Tons

1200 CFM

3 Tons

1200 CFM

5 Tons

2000 CFM

5 Tons

2000 CFM

5 Tons

2000 CFM

1-1/2

600

ON

OFF

OFF

X

X

X

2

800

OFF

ON

OFF

X

X

X

X

X

X

2-1/2

1000

ON

ON

OFF

X

X

X

X

X

X

3

1200

OFF

OFF

ON

X

X

X

X

X

X

3-1/2

1400

ON

OFF

ON

X

X

X

X

X

X

4

1600

OFF

ON

ON

X

X

X

5

2000

ON

ON

ON

X

X

X

X—Indicates allowable selection.

TABLE 9—CONTINUOUS FAN (CF) AIRFLOW SETUP SWITCH POSITION

CONTINUOUS

FAN (CFM)

CF SETUP

SWITCH POSITION

ALLOWABLE FURNACE MODEL SETUP

CF-1

CF-2

CF-3

042040

042060

042080

060080

060100

060120

Default

OFF

OFF

OFF

565*

515*

690*

690*

860*

1035*

600

ON

OFF

OFF

X

X

X

800

OFF

ON

OFF

X

X

X

X

X

X

1000

ON

ON

OFF

X

X

X

X

X

X

1200

OFF

OFF

ON

X

X

X

X

X

X

1400

ON

OFF

ON

X

X

X

X

X

X

1600

OFF

ON

ON

X

X

X

2000

ON

ON

ON

X

X

X

* Add 15% additional CFM when Bypass Humidifier switch SW-3 on control board is used.
X—Indicates allowable selection.

Fig. 45—Example of Setup Switch in OFF Position

A95198

1

OFF

—35—