NOTE:

Use AWG No. 18 color-coded copper thermostat wire for

lengths up to 100 ft. For wire lengths over 100 ft, use AWG No.
16 wire.

NOTE:

For 2-speed applications, refer to Sequence of Operation

section.

III.

ACCESSORIES

1. Electronic Air Cleaner (EAC)

The control center EAC terminals are energized with 115v
(1.5-amp maximum) during blower operation.
a. Two extension leads are connected to the control center

EAC terminals to assist field installation of an EAC. (See
Fig. 25.) To use these leads, proceed with the following:

(1.) Strip EAC power lead insulation approximately 1/4

in.

(2.) Insert stripped end into factory-supplied black

lead’s butt connector and crimp to secure.

(3.) Strip EAC neutral lead insulation approximately 1/4

in.

(4.) Insert stripped end into factory-supplied white

leads’s butt connector and crimp to secure.

NOTE:

If desired, cut butt connectors off factory leads and strip

insulation approximately 1/4 in and use field-supplied wire nuts to
connect.

b. An alternate method to attach EAC lead to control center

is the following procedure:

(1.) Remove 2 screws securing the control box to

furnace blower shelf.

(2.) Remove and discard 2 factory-supplied leads from

control center EAC terminals.

(3.) Strip EAC power leads insulation approximately

1/8 in.

NOTE:

The control center EAC terminals are sized for 12 gage

maximum, solid or stranded wire.

(4.) Route EAC leads through right-hand wire grommet.

TABLE 4—ELECTRICAL DATA

UNIT

SIZE

VOLTS—
HERTZ—

PHASE

OPERATING

VOLTAGE RANGE

MAXIMUM

UNIT

AMPS

UNIT

AMPACITY†

MINIMUM

WIRE

SIZE

MAXIMUM WIRE

LENGTH (FT)‡

MAXIMUM FUSE OR

CKT BKR AMPS**

Maximum*

Minimum*

042040

115—60—1

127

104

8.9

12.0

14

31

15

042060

115—60—1

127

104

8.9

12.0

14

31

15

042080

115—60—1

127

104

8.9

12.0

14

31

15

060080

115—60—1

127

104

13.8

17.9

12

32

20

060100

115—60—1

127

104

13.8

18.1

12

32

20

060120

115—60—1

127

104

11.6

15.3

12

37

20

* Permissible limits of voltage range at which unit will operate satisfactorily.
† Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier, etc.) full load

amps.

‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
** Time-delay fuse is recommended.

Fig. 25—Control Center

A93062

W2

COM

24V

W/W1

Y/Y2

RG

HUM

HOT SURFACE
IGNITOR CONNECTOR

EAC-ELECTRONIC AIR

CLEANER TERMINALS

(115-VAC 1 AMP MAX)

115-V
CONNECTORS

24-V THERMOSTAT
TERMINALS

PRESSURE SWITCH
CONNECTOR

HUM-HUMIDIFIER
TERMINAL
(24-VAC 0.5 AMP MAX)

TRANSFORMER

24-V CONNECTORS

3-AMP FUSE

STATUS AND DIAGNOSTIC
LED LIGHTS

AIR CONDITIONING
(A/C) SETUP SWITCH
SETUP SWITCHES
(SW) AND BLOWER
OFF DELAY SETUP
SWITCHES
MODEL PLUG

COMMUNICATION

CONNECTOR

CONTINUOUS

FAN (CF) SETUP

SWITCHES

MAIN BLOWER

CONTROL WIRE

CONNECTOR

DEHUMIDIFIER (DH)
CONNECTOR