Table 11—Orifice Size* And Manifold Pressure For Gas Input Rate (Continued)

(Tabulated Data Based On 21,000 Btuh Per Burner, Derated 4 Percent For Each 1000 Ft Above Sea Level)

ALTITUDE

RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

Only

9001

to

10,000

600

43

2.4

43

2.5

43

2.6

43

2.7

625

43

2.3

43

2.3

43

2.4

43

2.5

650

43

2.1

43

2.2

43

2.2

43

2.3

675

48

3.6

48

3.8

43

2.1

43

2.1

700

48

3.4

48

3.5

48

3.6

48

3.7

725

49

3.7

49

3.8

48

3.4

48

3.5

* Orifice numbers 43 are factory installed