Page 12

background image

DUCTWORK ACOUSTICAL TREATMENT

Metal duct systems that do not have a 90 degree elbow and 10 ft
of main duct to the first branch take-off may require internal
acoustical lining. As an alternative, fibrous ductwork may be used
if constructed and installed in accordance with the latest edition of

SMACNA construction standard on fibrous glass ducts. Both
acoustical lining and fibrous ductwork shall comply with NFPA
90B as tested by UL Standard 181 for Class 1 Rigid air ducts.

Table 3—Opening Dimensions (In.)

FURNACE

CASING

WIDTH

APPLICATION

PLENUM OPENING

FLOOR OPENING

A

B

C

D

14–3/16

Upflow Applications on Combustible or Noncombustible

Flooring (KGASB subbase not required)

12-11/16

21-5/8

13-5/16

22-1/4

Downflow Applications on Noncombustible Flooring

(KGASB subbase not required)

12-9/16

19

13-3/16

19-5/8

Downflow applications on combustible flooring (KGASB

subbase required)

11-13/16

19

13-7/16

20-5/8

Downflow Applications on Combustible Flooring with CD5 or

CK5 Coil Assembly or KCAKC coil box (KGASB subbase

not required)

12-5/16

19

13-5/16

20

17–1/2

Upflow Applications on Combustible or Noncombustible

Flooring (KGASB subbase not required)

16

21-5/8

16-5/8

22-1/4

Downflow Applications on Noncombustible Flooring

(KGASB subbase not required)

15-7/8

19

16-1/2

19-5/8

Downflow applications on combustible flooring (KGASB

subbase required)

15-1/8

19

16-3/4

20-5/8

Downflow Applications on Combustible Flooring with CD5 or

CK5 Coil Assembly or KCAKC coil box (KGASB subbase

not required)

15-1/2

19

16-1/2

20

21

Upflow Applications on Combustible or Noncombustible

Flooring (KGASB subbase not required)

19-1/2

21-5/8

20-1/8

22-1/4

Downflow Applications on Noncombustible Flooring

(KGASB subbase not required)

19-3/8

19

20

19-5/8

Downflow applications on combustible flooring (KGASB

subbase required)

18-5/8

19

20-1/4

20-5/8

Downflow Applications on Combustible Flooring with CD5 or

CK5 Coil Assembly or KCAKC coil box (KGASB subbase

not required)

19

19

20

20

24-1/2

Upflow Applications on Combustible or Noncombustible

Flooring (KGASB subbase not required)

23

21-1/8

23-5/8

22-1/4

Downflow Applications on Noncombustible Flooring

(KGASB subbase not required)

22-7/8

19

23-1/2

19-5/8

Downflow applications on Combustible flooring (KGASB

subbase required)

22-1/8

19

23-3/4

20-5/8

Downflow Applications on Combustible Flooring with CD5 or

CK5 Coil Assembly or KCAKC coil box (KGASB subbase

not required)

22-1/2

19

23-1/2

20

Fig. 14—Duct Flanges

A02329

UPFLOW

OWNFLOW

HORIZONTAL

PREFERRED

PERMITTED

PREFERRED

PREFERRED

PREFERRED

120˚

MIN

PREFERRED

120˚

MIN

PREFERRED

120˚

MIN

90˚

90˚

PERMITTED

PERMITTED

D

11

This manual is related to the following products: