Table 1D —524J***H Physical Data, SI — Heat Pump Units

LEGEND

UNIT 524J*

07H

08H

12H

NOMINAL CAPACITY (kW)

21

26

35

OPERATING WEIGHT (kg)

Base Unit with TXV

175

175

194

Plenum

80

80

80

FANS

Qty...Diam. (mm)

1...381

1...381

1...381

Nominal Airflow (L/s)

1133

1604

1888

Airflow Range (L/s)

850-1416

1203-2006

1416-2360

Nominal Motor kW (Standard Motor)

208/230-1-60

0.97

1.79

208/230-3-60 and 460-3-60

1.79

1.79

1.79

575-3-60

0.75

1.49

1.49

Motor Speed (r/s)

208/230-1-60

28.8

28.8

208/230-3-60 and 460-3-60

28.8

28.8

22.8

575-3-60

28.8

28.8

22.8

REFRIGERANT

R-410A

Operating charge (kg)

(approx per circuit)

1.36

1.36

0.91/0.91

DIRECT-EXPANSION COIL

Enhanced Copper Tubes, Aluminum Sine-Wave Fins

Max Working Pressure (kPag)

3102

Face Area (sq m)

0.77

0.77

0.93

No. of Splits

1

1

2

No. of Circuits per Split

12

15

9

Split Type...Percentage

Rows...Fins/m

3...591

3...591

3...591

PIPING CONNECTIONS,

Quantity...Size (in.)

DX Coil — Suction (ODF)

1...1

1

/

8

1...1

1

/

8

2...1

1

/

8

DX Coil — Liquid Refrigerant (ODF)

1...

5

/

8

1...

5

/

8

2...

5

/

8

Steam Coil, In (MPT)

1...2

1

/

2

1...2

1

/

2

1...2

1

/

2

Steam Coil, Out (MPT)

1...1

1

/

2

1...1

1

/

2

1...1

1

/

2

Hot Water Coil, In (MPT)

1...1

1

/

2

1...1

1

/

2

1...1

1

/

2

Hot Water Coil, Out (MPT)

1...1

1

/

2

1...1

1

/

2

1...1

1

/

2

Condensate (PVC)

1...1

1

/

4

ODM/1 IDF

FILTERS

Throwaway —

Factory Supplied

Quantity...Size (mm)

4...406 x 610 x 51

Access Location

Either Side

STEAM COIL**

Max Working Pressure (kPag at 126°C)

138

Total Face Area (sq m)

0.62

0.62

0.62

Rows...Fins/m

1...355

1...355

1...355

HOT WATER COIL**

Max Working Pressure (kPag)

1034

Total Face Area (sq m)

0.62

0.62

0.62

Rows...Fins/m

2...335

2...335

2...335

Water Volume

(L)

31.4

(m

3

)

0.031

DX

Direct Expansion

TXV

Thermostatic Expansion Valve

Units are shipped without refrigerant charge.