Table 4 — Electrical Data, Standard Motors
See Legend and Notes on page 18.
Table 5 — Electrical Data, Alternate Motors
See Legend and Notes on page 18.
UNIT
V*-PH-Hz
VOLTAGE
LIMITS
FAN MOTOR
POWER SUPPLY
Hp (kW)
FLA
Minimum
Circuit Amps
MOCP
524J*A07A
524J*A07H
208/230-1-60
187-253
1.3 (0.97)
7.6
9.5
15
208/230-3-60
187-253
2.4 (1.79)
5.8
7.3
15
460-3-60
414-506
2.4 (1.79)
2.6
3.3
15
575-3-60
518-632
1.0 (0.75)
1.4
1.7
15
524J*08A
524J*08H
208/230-1-60
187-253
2.4 (1.79)
11.0
13.8
20
208/230-3-60
187-253
2.4 (1.79)
5.8
7.3
15
460-3-60
414-506
2.4 (1.79)
2.6
3.3
15
575-3-60
518-632
2.0 (1.49)
2.4
8.0
15
524J*12A
524J*12H
208/230-3-60
187-253
2.4 (1.79)
5.8
7.5
15
460-3-60
414-506
2.4 (1.79)
2.6
3.3
15
575-3-60
518-632
2.0 (1.49)
2.4
3.0
15
524J*14A
208/230-3-60
187-253
2.4 (1.79)
5.8
7.5
15
460-3-60
414-506
2.4 (1.79)
2.6
3.3
15
575-3-60
518-632
3.0 (2.24)
3.8
4.8
15
524J*16A
208/230-3-60
187-253
3.7 (2.76)
10.6
13.3
20
460-3-60
414-506
3.7 (2.76)
4.6
6.0
15
575-3-60
518-632
3.0 (2.24)
3.8
4.8
15
UNIT
V*-PH-Hz
VOLTAGE
LIMITS
FAN MOTOR
POWER SUPPLY
Hp (kW)
FLA
Minimum
Circuit Amps
MOCP
524J*A07A
524J*A07H
208/230-1-60
187-253
2.4 (1.79)
11.0/11.0
13.8/13.8
20
208/230-3-60
187-253
2.9 (2.16)
7.5
9.4
15
460-3-60
414-506
2.9 (2.16)
3.4
4.3
15
575-3-60
518-632
2.0 (1.49)
2.4
3.0
15
524J*08A
524J*08H
208/230-1-60
187-253
2.4 (1.79)
11.0
13.8
15
208/230-3-60
187-253
2.9 (2.16)
7.5/7.5
9.4/9.4
15
460-3-60
414-506
2.9 (2.16)
3.4
4.3
15
575-3-60
518-632
3.0 (2.24)
3.8
4.8
15
524J*12A
524J*12H
208/230-3-60
187-253
3.7 (2.76)
10.5/10.5
13.3/13.3
20
460-3-60
414-506
3.7 (2.76)
4.8
6.0
15
575-3-60
518-632
3.0 (2.24)
3.8
4.8
15
524J*14A
208/230-3-60
187-253
3.7 (2.76)
10.2
12.7
20
460-3-60
414-506
3.7 (2.76)
4.8
6.0
15
575-3-60
518-632
5.0 (3.73)
5.1
6.4
15
524J*16A
208/230-3-60
187-253
5.0 (3.73)
14.6/12.8
18.3/16.0
30/25
460-3-60
414-506
5.0 (3.73)
6.4
8.0
15
575-3-60
518-632
5.0 (3.73)
5.1
6.4
15