Table 9E — Medium-Static Drive Data, 60 Hz — SI

Table 9F — High-Static Drive Data, 60 Hz — SI

UNIT

524J*07A

524J*07H

524J*08A

524J*08H

524J*12A

524J*12H

524J*14A

524J*16A

MOTOR DRIVE

Motor Pulley Pitch Diameter (mm)

86.4-

111.8

86.4-

111.8

86.4-

111.8

86.4-

111.8

94.0-

119.4

Pulley Factory Setting

Full Turns Open

2.5

2.5

2.5

2.5

3.0

FAN DRIVE

Pulley Pitch Dia (mm)

224

203

203

208

218

Pulley Bore (mm)

25.4

25.4

25.4

36.5

36.5

Belt No. — Section

1—A

1—A

1—A

1—A

1—B

Belt Pitch (mm)

1074

1024

1024

1049

1062

FAN SPEEDS (r/s)

Factory Setting

12.7

14.0

14.0

13.7

14.0

Range

11.1-14.4

12.2-15.8

12.2-15.8

11.9-15.4

12.4-15.7

Max Allowable Speed (r/s)

20.0

20.0

20.0

20.0

20.0

Change per

1

/

2

Turn of

Moveable Motor Pulley

Flange

0.328

0.360

0.360

0.352

0.278

MAX FULL TURNS FROM

CLOSED POSITION

5

5

5

5

6

SHAFTS CENTER DISTANCE (mm)

265-313

265-313

265-313

265-313

265-313

UNIT

524J*07A

524J*07H

524J*08A

524J*08H

524J*12A

524J*12H

524J*14A

524J*16A

MOTOR DRIVE

Motor Pulley Pitch Diameter (mm)

86.4-

111.8

86.4-

111.8

86.4-

111.8

94.0-

119.4

109.2-

134.6

Pulley Factory Setting

Full Turns Open

2.5

2.5

2.5

3.0

3.0

FAN DRIVE

Pulley Pitch Dia (mm)

178

152

152

188

201

Pulley Bore (mm)

25.4

25.4

25.4

36.5

36.5

Belt No. — Section

1—A

1—A

1—A

1—B

1—B

Belt Pitch (mm)

1049

947

947

1011

1011

FAN SPEEDS (r/s)

Factory Setting

16.0

18.7

18.7

16.3

17.7

Range

14.0-

18.1

16.3-

20.0

†‡

16.3-

20.0

14.4-

18.3

15.8-

19.5

Max Allowable Speed (r/s)

20.0

20.0

20.0

20.0

20.0

Change per

1

/

2

Turn of

Moveable Motor Pulley

Flange

0.410

0.478

0.478

0.323

0.307

MAX FULL TURNS FROM

CLOSED POSITION

5

5

5

6

6

SHAFTS CENTER DISTANCE (mm)

265-313

265-313

265-313

265-313**

232-279

Values for 3-phase motor shown. For single-phase motor, pulley pitch diameter is 178 mm

and resulting fan speed is 14.0-18.3 r/s.

It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 20 r/s.