Bryant Air Handling Units 524J User Manual
Page 33
33
Legend and Notes for Tables 10A and 10C
LEGEND
NOTES:
1. Maximum allowable fan speed is 1200 rpm for all sizes.
2. Fan performance is based on deductions for wet coil, clean 2-in.
filters, and unit casing. See table at right for factory-supplied filter
pressure drop.
3. Refer to fan motor and drive tables for additional data.
FACTORY-SUPPLIED PRESSURE DROP — ENGLISH
Legend and Notes for Tables 10B and 10D
LEGEND
ESP — External Static Pressure
NOTES:
1. Maximum allowable fan speed is 20 r/s for all sizes.
2. Fan performance is based on deductions for wet coil, clean
51-mm filters, and unit casing. See table at right for factory-sup-
plied filter pressure drop.
3. Refer to fan motor and drive tables for additional data.
FACTORY-SUPPLIED PRESSURE DROP — SI
Bhp
—
Brake Horsepower Input to Fan
ESP
—
External Static Pressure
UNIT
AIRFLOW
(Cfm)
PRESSURE DROP
(in. wg)
524J*07A
524J*07H
1,800
0.05
2,400
0.08
3,000
0.11
524J*08A
524J*08H
2,250
0.07
3,000
0.11
3,750
0.15
524J*12A
524J*12H
3,000
0.11
4,000
0.17
5,000
0.23
524J*14A
3,750
0.06
5,000
0.10
6,250
0.13
524J*16A
4,500
0.08
6,000
0.12
7,500
0.17
UNIT
AIRFLOW
(L/s)
PRESSURE DROP
(Pa)
524J*07A
524J*07H
850
13
1150
20
1450
28
524J*08A
524J*08H
1000
17
1400
27
1800
38
524J*12A
524J*12H
1450
28
1900
42
2350
56
524J*14A
1750
15
2350
24
2950
33
524J*16A
2100
20
2800
30
3500
42