Legend and Notes for Tables 10A and 10C

LEGEND

NOTES:

1. Maximum allowable fan speed is 1200 rpm for all sizes.

2. Fan performance is based on deductions for wet coil, clean 2-in.

filters, and unit casing. See table at right for factory-supplied filter

pressure drop.

3. Refer to fan motor and drive tables for additional data.

FACTORY-SUPPLIED PRESSURE DROP — ENGLISH

Legend and Notes for Tables 10B and 10D

LEGEND

ESP — External Static Pressure

NOTES:

1. Maximum allowable fan speed is 20 r/s for all sizes.

2. Fan performance is based on deductions for wet coil, clean

51-mm filters, and unit casing. See table at right for factory-sup-

plied filter pressure drop.

3. Refer to fan motor and drive tables for additional data.

FACTORY-SUPPLIED PRESSURE DROP — SI

Bhp

Brake Horsepower Input to Fan

ESP

External Static Pressure

UNIT

AIRFLOW

(Cfm)

PRESSURE DROP

(in. wg)

524J*07A

524J*07H

1,800

0.05

2,400

0.08

3,000

0.11

524J*08A

524J*08H

2,250

0.07

3,000

0.11

3,750

0.15

524J*12A

524J*12H

3,000

0.11

4,000

0.17

5,000

0.23

524J*14A

3,750

0.06

5,000

0.10

6,250

0.13

524J*16A

4,500

0.08

6,000

0.12

7,500

0.17

UNIT

AIRFLOW

(L/s)

PRESSURE DROP

(Pa)

524J*07A

524J*07H

850

13

1150

20

1450

28

524J*08A

524J*08H

1000

17

1400

27

1800

38

524J*12A

524J*12H

1450

28

1900

42

2350

56

524J*14A

1750

15

2350

24

2950

33

524J*16A

2100

20

2800

30

3500

42