START-UP CHECKLIST

(SPLIT SYSTEMS WITH 524J UNITS)

I. PRELIMINARY INFORMATION

OUTDOOR: MODEL NO. _________________________

SERIAL NO. ___________________________________

INDOOR: MODEL NO. ___________________________

SERIAL NO. ___________________________________

ADDITIONAL ACCESSORIES ______________________________________________________________________________

II. PRE-START-UP

OUTDOOR UNIT

IS THERE ANY SHIPPING DAMAGE? _______________

(Y/N) ____

IF SO, WHERE: _________________________________________________________________________________________

_______________________________________________________________________________________________________

WILL THIS DAMAGE PREVENT UNIT START-UP?

(Y/N) _____

CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT?

(Y/N) _____

HAS THE GROUND WIRE BEEN CONNECTED?

(Y/N) _____

HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY?

(Y/N) _______

ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY?

(Y/N) _______

HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED?

(Y/N) _____

CONTROLS

ARE THERMOSTAT(S) AND INDOOR FAN CONTROL WIRING

CONNECTIONS MADE AND CHECKED?

(Y/N) _____

ARE ALL WIRING TERMINALS (including main power supply) TIGHT?

(Y/N) _____

HAVE OUTDOOR UNIT CRANKCASE HEATERS BEEN ENERGIZED FOR 24 HOURS?

(Y/N) ______

INDOOR UNIT

HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE?

(Y/N) _____

ARE PROPER AIR FILTERS IN PLACE?

(Y/N) _____

HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? (Y/N) ______

DO THE FAN BELTS HAVE PROPER TENSION?

(Y/N) _____

PIPING

524J***A, 524J***H

HAS FOAM SHIPPING BLOCK BEEN REMOVED FROM THE TXV (Thermostatic Expansion Valve)?

(Y/N) ______

ARE LIQUID LINE SOLENOID VALVES LOCATED AT THE INDOOR UNIT (524J***A) OR OUTDOOR UNIT (524J***H)

COILS AS REQUIRED?

(Y/N) _______

HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CONDENSERS, INDOOR COILS,

TXVs (Thermostatic Expansion Valves) SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS

WITH A LEAK DETECTOR?

(Y/N) _____

LOCATE, REPAIR, AND REPORT ANY LEAKS. _______________________________________________________________

HAVE ALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED)

(Y/N) ____

ARE THE COMPRESSOR OIL SIGHT GLASSES SHOWING CORRECT LEVELS?

(Y/N) _____