FAIL POINT E 'BURNER LOCK

OUT'

Is the gas supply

connected and at the

correct pressure?

Remove boiler casing.

Reset and restart

the boiler.

Can a flame be seen

through the spyglass?

Note: there is a 20

second delay from fan

on to spark.

Yes

No

Rectify gas supply

problem.

No

TURN OFF GAS SUPPLY.

Remove inner casing

cover.

Reset and restart boiler.

Does a spark occur

across the electrodes?

No

Are the electrodes

and gap and

connections

in good order?

No

Repair or replace

spark electrode

or HT leads.

Yes

Replace control board.

Yes

During spark period

is there 216V D.C.
across the pins at

connector X2?

Replace gas valve or

check cable to it.

Yes

No

Yes

TURN OFF GAS SUPPLY.
Remove the combustion

chamber cover. Is the

sense (right) electrode

and lead in good

condition and is gap

correct?

See Section 15.4.3

No

Repair or replace

flame sense

or cable to it.

Replace control board.
Note: It is not possible

to reliably check the

cross light performance

of the burner.

In the unlikely event of

such a fault, investigate

condition of flue,

burner and injector.

Also check polarity of
mains voltage supply.

Yes

38

NOTE: Do not attempt to light the boiler

with the combustion chamber cover

removed.