Fa il point c, Fa il point d – Bosch 14/19CBI User Manual

Page 37

background image

FA

IL POINT C

Is the boiler in a very cold

environment

i.e is the primary water

temperature below 5°C?

Boiler is running in

'Autofroststat' mode.

Yes

Demand light has

failed. Replace control

board if it is

considered a problem.

No

FA

IL POINT D

Is the system fully

water pressurised

and is all air vented?

The system should have a

bypass fitted as described in

Section 7. SYSTEM and Figs.

5, 6 & 7. Is bypass fitted and

correctly adjusted?

Yes

Remove connector at X5.

With boiler cool is there a

short circuit between the

orange & black cables?

Reset the lockout and create

a boiler demand.

With the boiler cool does

the pump run?

Yes

Switch off mains supply.

Remove boiler cover

and inspect the

temperature sensor.

Is it correctly fitted to the

manifold with heat

conductive paste on its

surface?

Yes

Gain access to control board

and inspect the slide switch

at the front of the board.

In normal domestic

installation this switch

should be in the left

'normal' position.

Yes

Yes

Yes

Replace control board.

Rectify fault/leak.

No

Add or adjust system

bypass.

No

No

Replace pump or

check cables to it.

No

Refit sensor to

manifold or add heat

conductive paste.

No

Use a suitable

implement to push

switch to the 'normal'

left position. The

'heatstore' right position

is for commercial

applications only.

No

Replace overheat

thermostat or check

wiring to it.

37