Remove connector

X5 and test

resistance between

the red and violet

cables. Is the

resistance between

1 kohm and

30 kohm?

FA

IL POINT A

No

Yes

NOTE: It is normal to see only a
demand light if the boiler is hot
and the burner has temporarily

shut off.

Ensure boiler is cool and user

control set to maximum.

Replace sensor

or check

cables to it.

Gain access to the

control board.

Is there 230V at connector

X1 between pins SL & N?

Replace control board.

Yes

No boiler demand

from the heating

system. Investigate

system.

No

FA

IL POINT B

Gain access to the

control board.

Is there 230V at connector

X1 between pins

'PERM LIVE' & 'N'?

No permanent live

supply to control

board. Investigate

electrical supply from

external system.

No

Create a new demand.

Does the fan run?

Yes

No

Is there 230V

across the fan

terminals?

WARNING:

if NO, both fan

terminals will

be LIVE.

Does the

pump

run?

Check fuse F1

on the control

board.

Has it blown?

No

No

No

Replace fan.

Yes

Air pressure switch

is stuck on.

Replace air pressure

switch.

Yes

Replace fuse and

investigate cause.

Suggestions:

connections to (or

faults within) pump,

fan, gas valve,

system wiring,

possible board fault.

Yes

Does the fan run

continuously?

Fan cycles on & off.

Is there any sign of

blockage in the flue or

air pressure tubes?

No

Replace control board.

No

Yes

Yes

Clear blockage.

Yes

Air pressure switch not

changing over. Check flue and

air pressure sense tubes. Are

they clear and not damaged?

No

Repair fault.

Replace air pressure switch.

If this does not solve the

problem check the venturi in

the fan housing.

Yes