beautypg.com

Compressor rotation, Cooling, Main burners – Bryant 581C024--060 User Manual

Page 42: 581b ,c

background image

42

Compressor Rotation

On 3-phase units be certain that the compressor is rotating in the
proper direction. To determine whether or not compressor is

rotating in the proper direction:

1. Connect the service gauges to suction and discharge

pressure fittings.

2. Energize the compressor.
3. The suction pressure should drop and the discharge

pressure should rise, as is normal on any start-up.

If the suction pressure does not drop and the discharge pressure
does not rise to normal levels:

1. Note that the indoor fan (006 and 007 three-phase units

only) is probably also rotating in the wrong direction.

2. Turn off power to the unit and tag disconnect.
3. Reverse any two of the unit power leads.
4. Turn on power to the unit and energize the compressor.

The suction and discharge pressure levels should now move to
their normal start-up levels.
NOTE: When the compressor is rotating in the wrong direction,
the unit makes more noise and does not provide cooling.

Cooling

Set the space thermostat to the OFF position. Set the system
selector switch at COOL position and the fan switch at AUTO

position. Adjust the thermostat to a setting below room
temperature. The compressor starts when contactor closes.
Check the unit charge. Refer to Refrigerant Charge section.
Reset the thermostat at a position above room temperature. The
compressor will shut off. Evaporator fan will shut off after a

30--second delay.
To Shut Off Unit -- Set the system selector switch at OFF

position. Resetting the thermostat at a position above room

temperature shuts off the unit temporarily until the space
temperature exceeds the thermostat setting. Units are equipped

with a Cycle-LOC™ protection device. The unit shuts down on

any safety trip and remains off; an indicator light on the

thermostat comes on. Check the reason for the safety trip.

Main Burners

Main burners are factory set and should require no adjustment.
TO CHECK ignition of main burners and heating controls, move

thermostat set point above room temperature and verify that the
burners light and evaporator fan is energized. Check heating

effect, then lower the thermostat setting below the room

temperature and verify that the burners and evaporator fan turn
off.
Refer to Tables 35 and 36 for the correct orifice to use at high
altitudes.

Table 35—Altitude Compensation*

581B 036--072, 581C 024--060 Standard Units

72,000 AND

115 000 BTUH

150,000 BTUH

ELEVATION

115,000 BTUH

NOMINAL INPUT

150,000 BTUH

NOMINAL INPUT

ELEVATION

(ft)

Natural

Liquid

Natural

Liquid

(ft)

Natural

Gas

Liquid

Propane

Natural

Gas

Liquid

Propane

Gas

Orifice

Propane

Orifice

Gas

Orifice

Propane

Orifice

Orifice

Size†

Orifice

Size†

Orifice

Size†

Orifice

Size†

0-2,000

33

43

30

37

2,000

36

44

31

39

3,000

36

45

31

40

4,000

37

45

32

41

5,000

38

46

32

42

6,000

40

47

34

43

7,000

41

48

35

43

8,000

42

49

36

44

9,000

43

50

37

45

10,000

44

50

39

46

11,000

45

51

41

47

12,000

46

52

42

48

13,000

47

52

43

49

14,000

48

53

44

50

*As the height above sea level increases, there is less oxygen per cubic

foot of air. Therefore, heat input rate should be reduced at higher alti-

tudes.

†Orifices available through your Bryant distributor.

Table 36—Altitude Compensation* —

581B 036--072, 581C 024--060 Low NOx Units

ELEVATION

60,000 AND

90,000 BTUH

NOMINAL INPUT

120,000 BTUH

NOMINAL INPUT

ELEVATION

(ft)

Natural

Gas

Orifice

Size†

Liquid

Propane

Orifice

Size†

Natural

Gas

Orifice

Size

Liquid

Propane

Orifice

Size†

0-2,000

38

45

32

42

2,000

40

47

33

43

3,000

41

48

35

43

4,000

42

49

36

44

5,000

43

49

37

45

6,000

43

50

38

45

7,000

44

50

39

46

8,000

45

51

41

47

9,000

46

52

42

48

10,000

47

52

43

49

11,000

48

53

44

50

12,000

49

53

44

51

13,000

50

54

46

52

14,000

51

54

47

52

*As the height above sea level increases, there is less oxygen per cubic

foot of air. Therefore, the input rate should be reduced at higher alti-

tudes.

†Orifices are available through your local Bryant distributor.

581B

,C

This manual is related to the following products: