Table 18 — 558D072 Air Delivery — Horizontal Discharge Units (Standard Motor)

AIRFLOW

(Cfm)

STANDARD BELT DRIVE MOTOR

External Static Pressure (in. wg)

0.1

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

Rpm

Watts

Rpm

Watts

Rpm

Watts

Rpm

Watts

Rpm

Watts

Rpm

Watts

Rpm

Watts

Rpm

Watts

Rpm

Watts

1800

765

487

821

532

923

638

1019

843

1099

883

1178

1031

1249

1182

1316

1353

1382

1526

1900

802

539

854

585

953

700

1046

835

1126

965

1201

1106

1274

1275

1338

1439

1402

1621

2000

840

600

888

646

984

771

1073

907

1154

1047

1226

1990

1297

1361

1363

1534

1424

1718

2100

878

669

923

716

1015

843

1101

981

1182

1140

1252

1292

1320

1456

1388

1639

1448

1831

2200

916

739

958

795

1046

924

1129

1072

1209

1241

1280

1404

1345

1569

1410

1744

1473

1945

2300

954

827

993

883

1079

1022

1160

1173

1237

1344

1309

1517

1372

1691

1434

1866

1496

2067

2400

993

916

1029

973

1112

1123

1190

1275

1264

1447

1336

1639

1400

1823

1459

1997

1519

2188

2500

1031

1022

1066

1081

1145

1241

1220

1396

1292

1569

1363

1770

1428

1962

1486

2145

1543

2335

2600

1070

1131

1103

1199

1179

1353

1251

1517

1322

1700

1390

1901

1456

2102

1514

2300

1569

2487

2700

1109

1258

1140

1318

1212

1482

1283

1656

1352

1849

1418

2041

1483

2257

1543

2462

2800

1148

1396

1177

1465

1246

1621

1316

1805

1383

1997

1446

2188

1510

2403

2900

1188

1543

1215

1604

1281

1770

1349

1962

1413

2154

1476

2352

1537

2562

3000

1227

1700

1253

1770

1316

1936

1382

2136

1444

2317

1506

2529

NOTES:
1. Boldface indicates field-supplied drive required. (See Note 7.)

2.

indicates field-supplied motor and drive are required.

3.

indicates maximum usable watts of a factory-supplied motor.

4. Maximum usable watts input is 2120. Extensive motor and electrical testing on these units ensures that the full range of the motor can be

utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected. For additional information on motor performance, refer to Table 4.

5. Values include losses for filters, unit casing, and wet coils.
6. Use of a field-supplied motor may affect wire sizing. Contact your distributor to verify.
7. Standard motor drive range: 1070 to 1460. All other rpms require field-supplied drive.
8. To convert watts to bhp:

watts input x motor efficiency

bhp =

746

Motor efficiency = .84

B. Belt Drive Motors

Fan motor pulleys are factory set for speed shown in Table 1.

To change fan speed:

1. Shut off unit power supply.

2. Loosen belt by loosening fan motor mounting nuts. See

Fig. 34.

3. Loosen movable pulley flange setscrew (see Fig. 35).

4. Screw movable flange toward fixed flange to increase speed

and away from fixed flange to decrease speed. Increas-
ing fan speed increases load on motor. Do not exceed maxi-
mum speed specified in Table 1.

5. Set movable flange at nearest keyway of pulley hub and

tighten setscrew. (See Table 1 for speed change for each
full turn of pulley flange.)

To align fan and motor pulleys:

1. Loosen fan pulley setscrews.

2. Slide fan pulley along fan shaft.

3. Make angular alignment by loosening motor from

mounting.

To adjust belt tension:

1. Loosen fan motor nuts.

2. Slide motor mounting plate away from fan scroll for proper

belt tension (

1

2

-in. deflection with one finger).

3. Tighten motor mounting nuts.

4. Adjust lock bolt and nut on mounting plate to secure

motor in fixed position.

C. Ventilation Sequence

If unit is equipped with economizer, the damper will open to
the minimum position whenever the evaporator fan runs.