Table 4 — Motor Data

UNIT
558D

EVAPORATOR-FAN

MOTOR

MAXIMUM

MAXIMUM

UNIT

VOLTAGE

MAXIMUM

CONTINUOUS

OPERATING

AMP

BHP*

WATTS*

DRAW

036

Std

.34

440

208/230

2.9

460

1.4

575

1.4

Alt

1.00

1000

208/230

5.1

460

2.3

575

2.3

048

Std

.75

850

208/230

3.7

460

1.9

575

1.9

Alt

1.00

1000

208/230

5.1

460

2.3

575

2.3

060

Std

1.20

1340

208/230

6.2

460

3.4

575

3.4

Alt

1.3

1750

208/230†

7.6

2.4

2120

208/230**

6.1

460

2.7

575

2.7

072

Std

2.40

2120

208/230

6.1

460

2.7

575

2.7

LEGEND

Bhp — Brake Horsepower

*Extensive motor and electrical testing on these units ensures that the full range of the motors can be

utilized with confidence. Using your fan motors up to the ratings shown in this table will not result in
nuisance tripping or premature motor failure. Unit warranty will not be affected.

†Single-Phase motor.
**3-phase motor.

Table 5 — 558D036 Air Delivery — Vertical Discharge Units (Standard Motor)

AIRFLOW

(Cfm)

STANDARD DIRECT DRIVE MOTOR

Low Speed

High Speed

208 v

230, 460, 575 v

208 v

230, 460, 575 v

ESP

Watts

ESP

Watts

ESP

Watts

ESP

Watts

900

0.67

253

0.68

277

0.69

307

0.69

363

1000

0.60

270

0.61

292

0.61

321

0.63

374

1100

0.55

287

0.56

307

0.57

335

0.58

385

1200

0.51

304

0.51

323

0.52

349

0.53

397

1300

0.45

321

0.46

338

0.46

364

0.47

408

1400

0.38

338

0.41

354

0.43

378

0.43

420

1500

0.34

355

0.36

369

0.38

392

0.39

431

LEGEND

ESP — External Static Pressure (in. wg)

NOTES:
1. Values include losses for filters, unit casing, and wet coils.
2. Extensive motor and electrical testing on these units ensures that the full range of the motor can be

utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not be affected. For additional in-
formation on motor performance, refer to Table 4.

3. Use of a field-supplied motor may affect wire sizing. Contact your distributor to verify.
4. To convert watts to bhp:

watts input x motor efficiency

bhp =

746

Motor efficiency = .63

—20—