Bryant Single Package Rooftop Electric Heating/Electric Cooling Unit 558D User Manual
Page 23
Table 10 — 558D060 Air Delivery — Vertical Discharge Units (Alternate Motor)
AIRFLOW
(Cfm)
ALTERNATE BELT DRIVE MOTOR
External Static Pressure (in. wg)
0.1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
Rpm
Watts
Rpm
Watts
Rpm
Watts
Rpm
Watts
Rpm
Watts
Rpm
Watts
Rpm
Watts
Rpm
Watts
Rpm
Watts
Rpm
Watts
1500
730
347
789
409
896
542
990
685
1072
848
1153
1022
1221
1196
1256
1328
1280
1349
1320
1400
1600
770
409
826
470
931
623
1020
766
1101
930
1178
1114
1252
1298
1311
1482
1340
1615
1380
1645
1700
811
480
865
552
966
705
1051
858
1133
1032
1205
1206
1278
1400
1345
1604
1397
1799
1424
1931
1800
852
562
905
634
1002
797
1084
950
1163
1124
1235
1318
1303
1512
1371
1727
1433
1942
1480
2136
1900
894
552
945
736
1037
899
1119
1063
1194
1237
1266
1431
1330
1625
1396
1850
1460
2074
1517
2299
2000
936
756
984
838
1072
1001
1154
1185
1226
1359
1297
1564
1362
1768
1422
1983
1485
2207
1544
2453
2100
978
869
1024
950
1108
1124
1192
1318
1259
1502
1327
1696
1393
1911
1452
2126
1510
2361
1569
2606
2200
1021
991
1064
1073
1145
1247
1225
1461
1294
1656
1359
1850
1423
2064
1483
2289
1538
2514
1595
2769
2300
1064
1124
1104
1206
1183
1390
1260
1604
1330
1819
1392
2013
1454
2228
1515
2463
1569
2698
1622
2943
2400
1107
1267
1145
1349
1222
1482
1296
1768
1365
1983
1426
2197
1485
2412
1544
2647
1601
2902
1652
3137
2500
1150
1420
1186
1512
1262
1717
1331
1931
1400
2166
1461
2391
1518
2606
1575
2841
1631
3096
1684
3352
NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 7.)
2.
indicates field-supplied motor and drive are required.
3.
indicates maximum usable watts of a factory-supplied motor.
4. Maximum usable watts input is 2120. Extensive motor and electrical testing on these units ensures that the full range of the motor can be
utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected. For additional information on motor performance, refer to Table 4.
5. Values include losses for filters, unit casing, and wet coils.
6. Use of a field-supplied motor may affect wire sizing. Contact your distributor to verify.
7. Alternate motor drive range: 900 to 1300. All other rpms require field-supplied drive.
8. To convert watts to bhp:
watts input x motor efficiency
bhp =
746
Motor efficiency = .74
Table 11 — 558C072 Air Delivery — Vertical Discharge Units (Standard Motor)
AIRFLOW
(Cfm)
STANDARD BELT DRIVE MOTOR
External Static Pressure (in. wg)
0.1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
Rpm
Watts
Rpm
Watts
Rpm
Watts
Rpm
Watts
Rpm
Watts
Rpm
Watts
Rpm Watts Rpm Watts Rpm Watts
1800
852
562
905
615
1002
739
1084
859
1163
998
1235
1156
1303
1318
1371
1499
1433
1638
1900
894
630
945
692
1037
818
1119
948
1194
1089
1266
1250
1330
1413
1396
1604
1460
1796
2000
936
708
984
771
1072
899
1154
1047
1226
1190
1297
1361
1362
1534
1422
1718
1485
1910
2100
978
795
1024
859
1108
998
1190
1156
1259
1310
1327
1473
1393
1656
1452
1840
1510
2041
2200
1021
891
1064
956
1145
1097
1225
1275
1294
1439
1359
1604
1423
1779
1483
1980
1538
2171
2300
1064
998
1104
1064
1183
1216
1260
1396
1330
1578
1392
1744
1454
1927
1515
2128
1569
2326
2400
1107
1114
1145
1182
1222
1353
1296
1534
1365
1718
1426
1901
1485
2084
1544
2283
1601
2459
2500
1150
1241
1186
1318
1262
1491
1331
1674
1400
1875
1461
2067
1518
2249
1575
2445
—
—
2600
1193
1387
1228
1465
1301
1648
1367
1831
1435
2041
1497
2240
1552
2428
—
—
—
—
2700
1237
1543
1269
1621
1341
1814
1404
1997
1471
2214
1532
2420
—
—
—
—
—
—
2800
1280
1718
1311
1796
1381
1989
1442
2180
1506
2394
—
—
—
—
—
—
—
—
2900
1324
1901
1354
1980
1420
2180
1481
2369
1542
2579
—
—
—
—
—
—
—
—
3000
1368
2093
1396
2171
1460
2369
1521
2571
—
—
—
—
—
—
—
—
—
—
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 7.)
2.
indicates field-supplied motor and drive are required.
3.
indicates maximum usable watts of a factory-supplied motor.
4. Maximum usable watts input is 2120. Extensive motor and electrical testing on these units ensures that the full range of the motor can be
utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected. For additional information on motor performance, refer to Table 4.
5. Values include losses for filters, unit casing and wet coils.
6. Use of a field-supplied motor may affect wire sizing. Contact your distributor to verify.
7. Standard motor drive range: 1070 to 1460. All other rpms require field-supplied drive.
8. To convert watts to bhp:
watts input x motor efficiency
bhp =
746
Motor efficiency = .84
—23—