d. After installation is complete, calculate the mini-

mum airflow across the economizer. To calculate the
minimum airflow, the following data is needed:
total cfm (cfm

3

), temperature of the total cfm (T

3

),

temperature of the return air (T

2

), and tempera-

ture of the entering outside air (T

1

). Cfm

1

is the

outside air cfm, which will be the minimum airflow.

Insert the data into the following equations:

T

1

(cfm

1

) + T

2

(cfm

2

)

= T

3

cfm

3

cfm

2

= (cfm

3

− cfm

1

)

Therefore:

T

1

(cfm

1

) + T

2

(cfm

3

− cfm

1

)

= T

3

cfm

3

Use this equation to determine cfm

1

, which is the

minimum airflow across the economizer.

(T

3

−T

2

) cfm

3

cfm

1

=

(T

1

− T

2

)

If cfm

1

does not match the desired minimum air-

flow from Step 1, readjust the minimum position
setting screw.

6. Determine the enthalpy changeover set point from

Fig. 28. The enthalpy changeover set point should be
set to return the outdoor air damper to the minimum
position when enthalpy rises above the set point. The
settings are A, B, C, and D. Set the enthalpy changeover
per the setting in Fig. 29.

7. Replace outdoor-air opening panel using screws from

Step 2. Replace filter access panel. Ensure the filter
access panel slides along the tracks and is securely en-
gaged. See Fig. 30.

8. Fasten hood top and side plate assembly (Fig. 31) to

outdoor-air opening panel with screws provided.

9. Slide outdoor-air inlet screen into screen track on hood

side plate. While holding screen in place, fasten screen
retainer to hood using screws provided. See Fig. 32.

NOTE:

Refer to Fig. 33 for PARABLADE economizer baro-

metric relief damper characteristics.

MINIMUM

POSITION

OPEN

3

1

T

P

P1

T1

4

2

5

S

S

O

D

C

TR

B

REV

. B

198818A

%

H

U

M

I

D

I

T

Y

90

70

60

30

10

D

C

B
A

60

65

70

75

55

50

85

80

DAMPER

DAMPER

CLOSED

OPEN

OUTDOOR TEMP

.

°

F

REV.

97-3672

CW–SETPOINTS–CCW

CONT

A
CTS SHO

WN IN HIGH ENTHALPY

RUSH A

T

24V

AC

3 mA

MIN.

A

T

1

1

VDC

CONT

ACT RA

TINGS: 1.5A

RUN, 3.5A

IN

OR UNPOWERED ST

AT

E

1

2

3

TR

TR1

24V

AC

ENTHALPY

CONTROL

Fig. 25 — Outdoor-Air Thermostat/

Enthalpy Control Installation

OAT — Outdoor-Air Thermostat
NOTE: See unit wiring diagram for details.

Fig. 26 — Wiring Connections for Outdoor-Air Thermostat

0.90

0.80

0.70

0.60

0.50

0.40

0.30

0.20

0.10

0.00

100

200

300

400

500

600

700

800

CFM

PRESSURE DROP

(in. wg)

Fig. 27 — Durablade Economizer Barometric Relief

Damper Characteristics