Page 21
Table 6 — 558D036 Air Delivery — Vertical Discharge Units (Alternate Motor)
AIRFLOW
(Cfm)
ALTERNATE BELT DRIVE MOTOR
External Static Pressure (in. wg)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Rpm
Watts
Rpm
Watts
Rpm
Watts
Rpm
Watts
Rpm
Watts
Rpm
Watts
Rpm
Watts
Rpm
Watts
900
581
119
673
179
736
219
805
249
865
288
911
338
957
388
988
428
1000
644
189
709
219
782
279
835
298
900
348
937
378
992
438
1039
487
1100
687
219
746
259
806
298
867
348
929
398
964
398
1013
487
1068
547
1200
733
259
785
318
843
348
903
408
960
467
994
497
1045
557
1090
637
1300
754
288
826
378
891
428
942
477
991
527
1047
597
1075
637
1122
696
1400
810
348
868
448
937
507
984
567
1032
617
1067
666
1110
726
1160
766
1500
841
418
911
527
985
607
1029
656
1073
716
1109
766
1150
816
1190
855
AIRFLOW
(Cfm)
ALTERNATE BELT DRIVE MOTOR
External Static Pressure (in. wg)
0.9
1.0
1.1
1.2
Rpm
Watts
Rpm
Watts
Rpm
Watts
Rpm
Watts
900
1039
448
1061
487
1083
527
1105
567
1000
1061
507
1086
547
1111
587
1136
627
1100
1090
577
1109
607
1127
637
1145
666
1200
1109
647
1156
676
1203
706
1250
736
1300
1152
716
1190
756
1228
796
1266
836
1400
1181
806
1237
845
1293
885
1349
925
1500
1225
895
1271
945
1317
995
1363
1044
NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 7.)
2.
indicates field-supplied motor and drive are required.
3.
indicates maximum usable watts of a factory-supplied motor.
4. Maximum usable watts input is 1000. Extensive motor and electrical testing on these units ensures that the full range of the motor can be
utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected. For additional information on motor performance, refer to Table 4.
5. Values include losses for filters, unit casing, and wet coils.
6. Use of a field-supplied motor may affect wire sizing. Contact your distributor to verify.
7. Alternate motor drive range: 760 to 1090 rpm. All other rpms require field-supplied drive.
8. To convert watts to bhp:
watts input x motor efficiency
bhp =
746
Motor efficiency = .75
Table 7 — 558D048 Air Delivery — Vertical Discharge Units (Standard Motor)
AIRFLOW
(Cfm)
STANDARD DIRECT DRIVE MOTOR
Low Speed
High Speed
208 v
230, 460, 575 v
208 v
230, 460, 575 v
ESP
Watts
ESP
Watts
ESP
Watts
ESP
Watts
1200
0.93
458
0.94
506
0.94
572
0.99
632
1300
0.86
471
0.87
521
0.87
589
0.92
651
1400
0.78
503
0.79
556
0.79
616
0.87
681
1500
0.70
536
0.73
593
0.73
631
0.80
698
1600
0.61
557
0.64
616
0.66
654
0.76
723
1700
0.51
584
0.54
646
0.58
678
0.68
750
1800
0.40
610
0.44
674
0.51
698
0.63
772
1900
0.29
629
0.37
696
0.46
720
0.56
796
2000
0.25
651
0.30
720
0.39
744
0.50
823
LEGEND
ESP — External Static Pressure (in. wg)
NOTES:
1. Values include losses for filters, unit casing, and wet coils.
2. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with
confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected. For additional information on motor performance, refer to Table 4.
3. Use of a field-supplied motor may affect wire sizing. Contact your distributor to verify.
4. To convert watts to bhp:
watts input x motor efficiency
bhp =
746
Motor efficiency = .66
—21—