Norgren VP51 DeviceNet Installation Instructions User Manual

Page 7

background image

7

Parameter

No.

Name Format

Default
Value

Class
Id

Instance
Id

Attribute
Id

Byte
length

4 Actual

Pressure

Read only integer, 0-4095
0 = minimum (zero) pressure
4095 = full scale output + 5%
span
(same as polled input)

- 4

13
(0x0D)

3 2

5 Status

Byte

Read only byte (same as
polled input)

- 4

13(0x0D)

3 1

6

Speed

Selectable integer, 0-7
0 = fastest, 7 = slowest
See fig. 1

0 3

1 104

(0x68)

1

7

Prop Gain

Selectable integer 0-7
0 = low gain, 7 = high gain
(see note 3) See fig. 3

4 3

1 105

(0x69)

1

8

Int Gain

Selectable integer 0-7
0 = low gain, 7 = high gain
(see note 3) See fig. 3

4 3

1 106

(0x6A)

1

9 Dither

Amplitude

Selectable integer 0-7
0 = no dither, 7 = maximum
dither

4 3

1 107

(0x6B)

1

10

Error Limit

Selectable 0=105% (0-4095)
0 = Error Limit Off
105% = Full scale output + 5%

10%
(390)

3 1

109
(0x6D)

1

11

Error Delay Integer 0-999

Set in 100ths of a second

200
(2 secs)

3 1

110
(0x6E)

2

12 Threshold

A

Selectable 0-105% (0-4095)
0 = Status Bit 2 always set
105% = Full scale output + 5%

50%
(1950)

3 1

111
(0x6F)

1

13 Threshold

B

Selectable 0-105% (0-4095)
0 = Status Bit 3 always set
105% = Full scale output + 5%

100%
(3900)

3 1

112
(0x70)

1

14 Pressure

Units

Selectable from:
Bar, psi, kPA, Atm, kg/cm^2
Sets units for pressure display
on LCD

Depends
on part
number

3 1

108
(0x6C)

1

15 Signal

Failure
Mode

Selectable from Fail Safe, Fail
Freeze
Sets operation of device on
loss of polled signal from
network (see note 2).

Fail Safe

3

1

113
(0x71)

1

Notes:

1) If the baud rate parameter is set to Autobaud the Device will automatically listen to the network and

work out the correct baud rate. The baud rate parameter will then automatically be set to the
appropriate baud rate and will remain at its new setting even after removing power from the Device. In
order to run the Autobaud function again, the baud rate must be changed back to Autobaud via
DeviceNet or via the keypad.

2) Demand Pressure can only be set by means of a polled I/O message. It can be read but not set by

explicit messaging. If no polled message is received, the output pressure is set according to parameter
15 – Signal Failure Mode. If Fail Safe is selected, the output pressure will be zero when no polled
messages are being received. If Fail Freeze is selected, the output pressure will remain at its last set
value when no polled messages are being received.

3) To set the proportional gain, first set the integral gain to 0, then adjust the proportional gain to give the

best possible response time without causing unacceptable overshoot or oscillations.

Once proportional gain is set correctly, increase integral gain to achieve the best possible accuracy
without causing unacceptable hunting (slow oscillations) on the output. See figs 2 & 3.