I/o data, No. bytes, Notes – Norgren VP51 DeviceNet Installation Instructions User Manual
Page 6: Devicenet interface details, Devicenet parameters
6
6. DEVICENET INTERFACE DETAILS
I/O Data
Name I/O
Type
(see Note 1)
No.
Bytes
Format
Demand Pressure
Polled Output
2
12 bit integer (0 to 4095)
0 = minimum (zero) pressure
4095 = full scale output + 5% span
(see Note 2)
Actual Pressure
Polled Input
2
12 bit integer (0 to 4095)
0 = minimum (zero) pressure
4095 = full scale output + 5% span
(see Note 3)
Status Byte
Polled Input
1
Bit 0: Set if difference between Demand
Pressure and Actual Pressure exceeds Error
Limit (see parameter 10).
Bit 1: Set if Bit 0 has been set for longer
than Error Delay (see parameter 11).
Bit 2: Set if Actual Pressure
≥ Threshold A
(see parameter 12).
Bit 3: Set if Actual Pressure
≥ Threshold B
(see parameter 13).
Bits 4-7: Not used.
(See Note 3)
Notes
:
1) Inputs and Outputs are defined from the perspective of the DeviceNet network.
2) For 150 psi variant Demand Pressure value= 26 x (Required Pressure in psi), e.g. to output 100 psi, set
Demand Pressure value to 2600.
For 10 bar variant Demand Pressure value = 390 x (Required Pressure in bar), e.g. to output 6 bar, set
Demand Pressure value to 2340.
IMPORTANT - Only 12 of the 16 bits in the two Demand Pressure bytes are used. The four most
significant bits are ignored. Setting the Demand Pressure value above 4095 or below 0 may lead
to unpredicted output pressures.
3) If the polled input is read as a single value of 3 or more bytes, the two least significant bytes hold the
actual pressure and the third least significant is the status byte. For example, a returned value of
266044 (0x040F3C) represents an actual pressure of 0x0F3C = 3900 = 100% full scale and a status
byte of 0x04 = bit 2 set.
DeviceNet Parameters
The following parameters are available via a DeviceNet configuration tool (e.g. RSNetworx) or via DeviceNet
explicit messaging, using the class, instance, attribute and byte length details in the table. To use a DeviceNet
configuration tool, it is necessary to register the DeviceNet VP51 EDS file on the configuration tool. The EDS file
can be dow
.
Parameter
No.
Name Format
Default
Value
Class
Id
Instance
Id
Attribute
Id
Byte
length
1
Baud Rate
Selectable from:
Autobaud, 125Kb/s, 250Kb/s,
500Kb/s (see note 1)
Autobaud 3
1
2
1
2 Serial
number
Read only 4 byte integer
Factory
set
1 1
6
4
3 Demand
Pressure
Read only integer, 0-4095
0 = minimum (zero) pressure
4095 = full scale output + 5%
span
(same as polled output, see
note 2)
- 3
1 114
(0x72)
2