4.2Accuracy Results for Reactive Energy Load Performance

Figure 8. Reactive Energy Load Performance vs IEC 62053-23 Class 2 Standard

Power Factor

Load Current (A)

Current Dynamic Range (x:1)

Error

sin

= 1

100

1

-0.05%

10

10

-0.03%

1

100

-0.01%

0.2

500

-0.03%

0.1

1000

-0.02%

0.05

2000

-0.06%

0.03

3333

-0.06%

0.025

4000

-0.07%

Lagging sin

= 0.5

100

1

0.28%

10

10

0.16%

1

100

0.11%

0.2

500

0.09%

0.1

1000

0.06%

0.05

2000

-0.08%

Leading sin

= 0.5

100

1

-0.29%

10

10

-0.21%

1

100

-0.15%

0.2

500

-0.16%

0.1

1000

-0.16%

0.05

2000

-0.32%

Table 5. Reactive Energy Load Performance

-3

-2

-1

0

1

2

3

0.01

0.1

1

10

100

Pe

rc

e

n

t Er

ror (

%

)

Load Current (A)

sin

ࢥ = 1

Lagging sin

ࢥ = 0.5

Leading sin

ࢥ = 0.5

Note: CS5480, where U

n

= 240

V, max = 2.5

(100

A) at 50

Hz

IEC 62053-23 Class 2 Spec, sin

ࢥ = 0.5

IEC 62053-23 Class 2 Spec, sin

ࢥ = 1