Diagnostics and Service
Subject to change due to technical modifications.
© Copyright WIKA Alexander Wiegand GmbH & Co. KG / BRD
WIKA Alexander Wiegand GmbH & Co. KG · Alexander-Wiegand-Str. · 63911 Klingenberg ·
(09372) 132 - 710 · Fax - 706 · E-mail: [email protected] · www.wika.de
74
7
Diagnostics and Service
The following error messages can appear on devices with displays
(see chapter 2.1.3):
8
Disposal
If a failure cannot be repaired, the transmitter must be switched off.The op-
erator then must make sure, that it is only switched on again after the
failure has been repaired.
Repairs should only be carried out by the manufacturer. All other repairs or
modifications are unauthorized.
Error Code
Error
Error Correction Measures
E00
ROM-error
Return device to manufacturer
E01
Power supply error
Check power supply
E03
E
2
PROM communications error
Disconnect and reconnect power
supply
E04
Sensor’s temperature range was
exceeded
Return sensor’s temperature to
specified limits
E06
Sensor recognition
Disconnect and reconnect power
supply
E07
General communications error
between the sensor and the con-
trol interface unit
Check the connection between
the sensor and the control inter-
face unit
E08
Error E
2
PROM
send in transmitter for service
Please observe local guidlines and regulations when disposing of trans-
mitters that are no longer serviceable.
Please turn any recycleable components in to the appropriate local orga-
nizations.