Universal Pressure Transmitter UniTrans
Operation of Transmitters with Display
Subject to change due to technical modifications.
© Copyright WIKA Alexander Wiegand GmbH & Co. KG / BRD
WIKA Alexander Wiegand GmbH & Co. KG · Alexander-Wiegand-Str. · 63911 Klingenberg ·
(09372) 132 - 710 · Fax - 706 · E-mail: [email protected] · www.wika.de
70
6.5.3
Main Menu: Output
DAMPING
Damping
0 s active
DAMPING
DAMPING
DAMPING
DAMPING
MAIN MENU
OUTPUT
OUTPUT
DEFINITION
OUTPUT
DAMPING
OUTPUT
INVERT: OFF
OUTPUT
INVERT: ON
OUTPUT
ALARM/ERROR
OUTPUT
LIMITS
OUTPUT
CURRENT OFFSET
LIMITS
LIMITS
The current runs between 4 and 20 mA
Alarm condition when limits are reached;
It is necessary to restart device by
using reset or by shutting down power
(see 8.5.6).
Damping
40 s active
Damping
20 s active
Damping
5 s active
Damping
1 s active
Output is inverted (20 mA ... 4 mA)
Output is not inverted (4 mA ... 20 mA)
Alarm at 3.6 mA
(downscale)
Alarm at 21 mA
(upscale)
Measured value runs between 3.8 mA
and 20.5 mA. The current holds at the
limit when the sensing range is exceeded.
Query routine for
additional safety.
The output current is combined with an
assigned offset, which can have a maximum
of 0.4 mA.