WIKA UT-11 User Manual
Page 26
C
Universal Pressure Transmitter UniTrans
Operation of Transmitters with Display
P
u
bl
is
he
d 1
6
.2.
04
Subject to change due to technical modifications.
© Copyright WIKA Alexander Wiegand GmbH & Co. KG / BRD
WIKA Alexander Wiegand GmbH & Co. KG · Alexander-Wiegand-Str. · 63911 Klingenberg ·
(09372) 132 - 710 · Fax - 706 · E-mail: [email protected] · www.wika.de
65
6.4
Default Data (factory settings)
Function
Defaults
Display
Unit of measurement
(Line 1)
Line 2
Line 3
Pressure display (in bar)
Temperature display (in °C)
Sensor’s nominal pressure range (in bar)
Calibration
zero 4 mA
span 20 mA
nom. pressure range start
nom. pressure range end
Output
Damping
Inversion
Fault
Limits
I-offset
0 s
no
21 mA (upscale)
3.8 ... 20.5 mA
0 mA
Service password
no active password
Service mounting correction
not activated
Language
English
Evaluation
linear
density
yes
1 g/cm
3
Calibrated special measurement ranges i. e. 4 bar on a 6 bar transmit-
ter can be adjusted by factory pre-setting. A reset to default will reset
the sensor back to its nominal range (i. e. 6 bar). The factory pre-setting
gets lost.