beautypg.com

WIKA UT-11 User Manual

Page 32

background image

C

Universal Pressure Transmitter UniTrans

Operation of Transmitters with Display

P

u

bl

is

he

d 1

6

.2.

04

Subject to change due to technical modifications.

© Copyright WIKA Alexander Wiegand GmbH & Co. KG / BRD

WIKA Alexander Wiegand GmbH & Co. KG · Alexander-Wiegand-Str. · 63911 Klingenberg ·

(09372) 132 - 710 · Fax - 706 · E-mail: [email protected] · www.wika.de

71

6.5.4

Main Menu: Evaluation

Enter height values, which are each assigned a volumetric value of measure for tank
linearization. The linearization and the assignment of the 4 ... 20 mA output signal
areconverted into tank volumes using this value pair.

When the evaluations function is activated the Turn down becomes
inactive

MAIN MENU

EVALUATION

EVALUATION

FUCTIONS

EVALUATION

REF. TABLE

REF. POINT

INSERT

REF. POINT

DELETE

INSERT

INSERT

DELETE

DELETE

DELETE

The level value and volume value

always be adjusted or verified in

order to store a value pair.

TABLE

EDIT

TABLE

ACTIVATE ?

EVALUATION

LINEAR

LINEAR

ACTIVATE ?

EVALUATION

DENSITY

Entry of a new value pair

for the table used in

tank linearization

Entry of the level as a %

Entry of the associated

volume as a %

It is possible to enter up to

30 value pairs

The value pair for 0% (P0)

and 100% (P31) are fixed

The selected

tag (value pair)

is deleted

The upper limit

can only be veri-

fied, not altered

The lower limit

can only be veri-

fied, not altered

Selected tag

(value pair:

level/volume)

is altered

The preset

linearization table

is activated

The linear correlation

between input and

output is set

The density of

the medium is set

l

d=

This manual is related to the following products: