VS-44FO - Connecting the VS-44FO

Figure 5: DIP-Switch Settings

DIPS

Function

Description

RS-485 TERM

RS-485 line
termination

OFF for no RS-485 line termination
ON for RS-485 120

line termination

PROG

Firmware update

Set ON only to update device firmware

MACH # 1, 2, 3, 4

Self Address

Sets the MACHINE # (see

Section

5.3.1

)

The RS-485 TERM DIP-switch is used only when the RS-485 port is connected

(see

Section

5.3

). The first and last units on the RS-485 line (for example, the

controller and the last VS-44FO) must be terminated. The units in between must

not be terminated.

Set the PROG DIP-switch ON only while updating the unit firmware, otherwise the

switch must be OFF.

5.3

Connecting a PC or Controller to the RS-485 Port

You can operate the VS-44FO over the RS-485 port from a distance of up to 1200

meters (3900ft) using any device equipped with an RS-485 port (for example, a

PC). For successful communication, you must set the RS-485 machine number

and bus termination.

To connect a device with a RS-485 port to the VS-44FO:

On the PC, connect the A (+) pin on the RS-485 port to the A (+) pin on the

RS-485 port on the rear panel of the VS-44FO

On the PC, connect the B (

–) pin on the RS-485 port to the B (–) pin on the

RS-485 port on the rear panel of the VS-44FO

On the PC, connect the G pin on the RS-485 port to the G pin on the RS-485

port on the rear panel of the VS-44FO