Smart-UPS RT 15000/20000 VA 230 Vac Stack/Rack-Mount 6U User Manual

General

Fault

Shutdown Due To Low

Battery.

The UPS shutdown while on battery

operation.

No corrective action is necessary.
Note: Should this situation reoccur,

consider increasing battery capacity.

Bypass Not Available Input

Freq/Volt out Of Range.

The frequency or voltage is out of

acceptable range for bypass. This

message occurs when the UPS is

online.

Correct the input voltage to

acceptable frequency or voltage.

Mains Not Available. Input

Frq/Volt Out of Range.

The frequency or voltage is out of

acceptable range for normal

operation.

Emergency PSU Fault.

Redundant Emergency Power Supply

Unit (PSU) is not working. Internal

diagnostic fault. The UPS will

continue to operate normally.

Contact APC Customer Support.

Refer to Contact Information in this

manual.

Fan Fault

A fan has failed.

Contact APC Customer Support.

Refer to Contact Information in this

manual.

Static Bypass Switch Fault.

The static bypass switch has failed.

System Failure Detected by

Surveillance.

The system has detected an internal

error.

Check for other alarms.
If the problem persists contact APC

Customer Support. Refer to Contact

Information in this manual.

System Not Synchronized

to Bypass.

System cannot synchronize to bypass

mode.Bypass mode may be

unavailable.

Option 1) Decrease input frequency

sensitivity.
Contact APC Customer Support.

Refer to Contact Information in this

manual.
Option 2) Correct bypass input

voltage to provide acceptable

frequency or voltage.

UPS In Bypass Due To

Fault.

The UPS has transferred to bypass

mode due to a fault.

Contact APC Customer Support.

Refer to Contact Information in this

manual.

UPS In Bypass Due To

Overload.

The load has exceeded the power

capacity.

Decrease the load.

UPS Is Overloaded.

The load has exceeded the system

power capacity.

Option 1) Decrease the load.
Option 2) Check the load distribution

on the three phases through the

PowerView display. If the load is

unevenly distributed, adjust the load

distribution.

Condition

PowerView Display

Message

Reason for Message

Corrective Action