24

Smart-UPS RT 15000/20000 VA 230 Vac Stack/Rack-Mount 6U User Manual

General

Status

# of batteries increased.

At least one battery pair has been

added to the system.

No corrective action is necessary.

# of batteries decreased.

At least one battery pair has been

removed from the system.

# External Battery Packs

increased.

At least one external battery pack has

been connected to the UPS.

# External Battery Packs

decreased.

At least one external battery pack has

been disconnected from the UPS.

Module

Failure

Bad Battery Pair.

A battery pair has failed and requires

replacement.

Refer to battery pair installation in

the external battery pack user

manual.

Threshold

Alarm

Load Power Is Above

Alarm Limit.

The load has exceeded the user-

specified load alarm threshold.

Option 1) Use the display interface to

raise the alarm threshold.
Option 2) Reduce the load

Load Is No Longer Above

Alarm Threshold.

The load exceeded the alarm

threshold. The situation has been

corrected. Either because the load

decreased or the threshold was

increased.

No corrective action is necessary.

Min Runtime Restored.

The system runtime dropped below

the configured minimum and has been

restored:
1) Additional battery modules were

installed.
2) The existing battery modules were

recharged.
3) The load was reduced.
4) The user- specified threshold was

decreased.

Condition

PowerView Display

Message

Reason for Message

Corrective Action