beautypg.com

Air sensor >6, Ke2 evaporator, Installation & wiring – Nor-Lake Enviro-Control IOM User Manual

Page 3: Location, Return air figure 2 - return air sensor placement

background image

KE2 Evaporator

Installation Instructions

.

s

u

t

a

t

s

m

e

t

s

y

s

r

o

/

d

n

a

e

r

u

t

a

r

e

p

m

e

t

m

o

o

r

e

h

t

f

o

g

n

i

w

e

i

v

y

s

a

e

r

o

f

See Figure 1 for locations.

If installing the controller on the face of the evaporator, preexist-

ing knockouts on the evaporator should be used for installing

the high voltage wiring. If knockouts do not preexist, hole(s)

may be carefully cut into an unobstructed area of the evapora-

tor case. If modifying the face of the evaporator is not feasible

or desired, the controller’s conduit knockouts may be used with

½ inch conduit.

The bottom side of the controller includes a cutout with cable

tie slots providing a strain relief for the low voltage and sensor

wires. Additional knockouts are available on either side if con-

duit is preferred.

Installation & Wiring

The KE2 Evap is supplied with pluggable connectors for all

connections. Pluggable connectors permit the controller to

be placed in a safe location while the wiring is installed. They

also simplify the wiring, allowing the wires to be fastened to the

screw terminals in the open air. Once all wiring is completed

using accepted wiring practices, it is plugged into the controller

Although there is one pressure transducer and four temperature

sensor inputs, when used with mechanical valves (TEVs), KE2

Evap only requires the (2) sensors supplied with the kit. One

sensor reads the return air temperature and the other measures

the coil temperature. NOTE! Sensor location is critical to the

proper operation of the controller.

Return Air Temperature Sensor - The air temperature sensor is

installed in the return air of the evaporator using the included

sensor mount. Most applications allow the sensor mount to

be installed using an existing screw. On evaporators where us-

ing an existing screw is not possible, the included self-tapping

screw may be used to secure the sensor mount to the evapora-

tor. Note: Be careful to avoid damage to an evaporator tube

or causing a leak in the drip pan. When installing, it is impor-

tant to prevent the air sensor from coming into contact with the

mounting bracket, cable ties, or any other solid material. Figure

2 shows an example of how to mount the sensor. The sensor

must be a minimum of 6 inches from the coil surface.

Location

The KE2 Evap was developed with ease of installation in mind.

The controller is supplied in an enclosure, and encapsulated to

protect the circuitry from moisture damage. This extra level of

protection allows the controller to be installed in the refriger-

ated space.

When installing the controller, it may either be installed on an

interior/exterior wall or on the evaporator. Many evaporators

evaporator or on its housing. Locating the controller as close to

the evaporator as possible reduces the amount of wiring when

converting existing systems, as well as when it is applied on new

applications.

-

tion providing easy access -- on the wall or near the entrance.

This enables the user to easily view the display, and eliminates

the need to use a ladder or lift to modify the setpoints or check

alarms.

If viewing the temperature outside the walk-in or refrigerated

room is desirable, the KE2 Evap may be used as a digital thermo-

stat. The controller is then installed near the door of the space

KE2 EvaporatorEfficiency

TM

thermsolutions

ENTER

BACK

2

2

KE2 EvaporatorEfficiency

TM

thermsolutions

ENTER

BACK

2

2

KE2 EvaporatorEfficiency

TM

thermsolutions

ENTER

BACK

2

2

On the wall

On the evaporator

At the entrance

Figure 1 - KE2 Evap Installation Locations

Air

Sensor

>6”

Return Air

Figure 2 - Return Air Sensor Placement

3

01/13 Rev. A 151627

Enviro-Control™