Ke2 evaporator efficiency, Setpoints menu, Parameter name description range default current – Nor-Lake Enviro-Control IOM User Manual

Page 14: Installation instructions, Enviro-control

background image

KE2 EvaporatorEfficiency

Installation Instructions

Parameter Name

Description

Range

Default

Current

ROOM TEMP

Room temperature to be maintained

-50°F to 90°F

-10°F

DEFROST TYPE

Method of defrost used on the evaporator coil: Electric, Air, Hot Gas with Liquid Line Solenoid/Compressor relay off, Hot Gas with

Liquid Line Solenoid/compressor relay on

ELEC, AIR, HOT GAS COMP ON, HOT GAS COMP OFF

ELEC

VALVE TYPE

Type of valve used on the system: mechanical, pre-configured electric, custom EEV configuration

MECHANICAL, KE2, SER/SEI 1 TO 20, SER B TO L, SEI 30, SEI 50, SEH, ETS12 TO 50,

ETS100, ETS250/400, KV, CAREL, CUSTOM;

MECHANICAL

Cust

om

EE

V O

nly

MOTOR TYPE

If VALVE TYPE = CUSTOM: The motor type used in the valve

BIPOLAR, UNIPOLAR

BIPOLAR

MOTOR STEP RATE

If VALVE TYPE = CUSTOM: The motor speed setting in number of steps per second

30 to 400 steps/second

200 steps

MAX VALVE STEPS

If VALVE TYPE = CUSTOM: The total number of steps required to move the valve from closed to fully open

200 to 6400 steps

1600 steps

SUPERHEAT

The superheat value that the controller will maintain, (not applicable if VALVE TYPE = MECHANICAL)

5°F to 30°F

8°F

MAX OPERATING PRES

The maximum allowable suction pressure, (not applicable if VALVE TYPE = MECHANICAL)

10 to 150 psig

150 psig

REFRIGERANT

The type of refrigerant used in the refrigeration system

404A, R507, 407A, 407C, 422A, 422D, 134A, R22, R717, 438A, 408A, 409A, 410A,

404A

AUX TEMP MODE

Configuration mode of the auxiliary temperature sensor

DISABLED, MONITOR, 2ND AIR TEMP, 2ND COIL TEMP

DISABLED

AUX RELAY MODE

Configuration mode of the auxiliary relay.

ALARM RELAY, 2 SPEED FAN CTL, 2ND COMP RELAY, 2ND FAN RELAY, 2ND DEFR

RELAY, LIGHT RELAY, CAMERA RELAY

ALARM RELAY

MIN COMP RUN TIME

Minimum amount of time the liquid line solenoid/compressor relay must remain on after it is energized

0 to 15 minutes

2 minutes

MIN COMP OFF TIME

Minimum amount of time the liquid line solenoid/compressor relay must remain off before it can be energized again.

0 to 15 minutes

5 minutes

REFRIG FAN MODE

Fan operation while in refrigeration mode

ON WITH COMPRESSOR, PERMANENT, CYCLE

ON WITH COMPRESSOR

DEFROST MODE

The method the controller uses to determine when to initiate a defrost.

DEMAND, SCHEDULED, RUN TIME

DEMAND

DEFROSTS / DAY

If DEFROST MODE = SCHEDULED: The number of evenly spaced defrosts per day the controller will initiate.

0 to 8

5

1ST DEFROST DELAY

If DEFROST MODE = SCHEDULED: The amount of time from controller power up until the first defrost is initiated.

0 to 240 minutes

120 minutes

DEFROST FAN STATE

Whether or not to run the evaporator fans during defrost

ON/OFF

OFF if DEFROST TYPE = ELEC, HOT GAS COMP ON, HOT GAS COMP OFF

ON if DEFROST TYPE = AIR

DEFROST TERM TEMP

The temperature the coil sensor(s) must exceed in order to terminate defrost. The defrost relay is de-energized at this point.

35°F to 90°F

50°F if DEFROST TYPE = ELEC, HOT GAS COMP ON, HOT GAS COMP OFF

40°F if DEFROST TYPE = AIR

DEFROST PARAMETER

The maximum amount of time the defrost relay will be energized.

0 to 90 minutes

25 minutes if DEFROST TYPE = ELEC

10 minutes if DEFROST TYPE = HOT GAS COMP ON, HOT GAS COMP OFF

40 minutes if DEFROST TYPE = AIR

DRAIN TIME

Time to be in drain mode (drip time)

0 to 15 minutes

2 minutes

COMP RUN TIME

If DEFROST MODE = RUN TIME: The amount of time liquid line solenoid/compressor relay is energized before the next defrost is initiated.

0 to 24 hours

6 hours

ELEC DEFROST MODE

If DEFROST TYPE = ELEC: Whether to leave the defrost relay energized during the defrost cycle or to utilize advanced defrost algorithm.

PULSE, PERMANENT

PULSE

FAN DELAY TEMP

After defrost, the coil sensor reading must fall below this temperature set point in order for the controller to resume normal fan operation.

-40°F to 35°F

20°F

MAX FAN DELAY TIME

Maximum amount of time after defrost to resume normal fan operation.

0 to 20 minutes

2 minutes

PUMP DOWN TIME

Minimum amount of time between de-energizing the liquid line solenoid/compressor relay and energizing the defrost relay.

0 to 10 minutes

0 minutes

MULTI AIR TEMP CTRL

Select control method to use with multiple room temperature sensors

AVERAGE, WARMEST

WARMEST

Bonded Con

tr

ol-

lers O

nly MULTI EVAP COOL

Select type of multi evaporator control - options are synchronous or independent

SYNC, INDEPENDENT

SYNC

MULTI EVAP DEFROST

Select whether to have all bonded controllers initiate defrost mode at the same time or independently.

SYNC, INDEPENDENT

SYNC

MULTI EVAP SENSOR

Select whether or not to share room temperature, coil temperature and suction pressure sensor data with bonded controllers.

SHARED, NOT SHARED

SHARED

HIGH TEMP ALARM OFFSET

The number of degrees above ROOM TEMP for a HIGH TEMP ALARM condition.

0°F to 99.9°F

10°F

HIGH TEMP ALARM DELAY

Minutes the room temperature must remain above ROOM TEMP + HIGH TEMP ALARM OFFSET before issuing a HIGH TEMP ALARM

0 to 120 minutes

60 minutes

LOW TEMP ALARM OFFSET

The number of degrees below ROOM TEMP for a LOW TEMP ALARM condition.

0°F to 20°F

4°F

LOW TEMP ALARM DELAY

Minutes the room temperature must remain below ROOM TEMP - LOW TEMP ALARM OFFSET before issuing a LOW TEMP ALARM

0 to 30 minutes

10 minutes

DOOR ALARM DELAY

If DIG IN (1, 2 and/or 3) MODE = DOOR SWITCH: The amount of time, in minutes, before an alarm condition is initiated if door is open and room

temperature is 5 degrees above ROOM TEMP + AIR TEMP DIFF

0 to 180 minutes

30 minutes

DIG IN 1 MODE

Sets the function of the digital input

DISABLED, 2ND ROOM TEMP, DOOR SWITCH, EXT ALARM, SYSTEM OFF

DOOR

DIG IN 1 STATE

Sets whether the switch activates when opened or closed

OPEN, CLOSED

CLOSED

DIG IN 2 MODE

Sets the function of the digital input

DISABLED, 2ND ROOM TEMP, DOOR SWITCH, EXT ALARM, SYSTEM OFF

DISABLED

DIG IN 2 STATE

Sets whether the switch activates when opened or closed

OPEN, CLOSED

CLOSED

DIG IN 3 MODE

Sets the function of the digital input

DISABLED, 2ND ROOM TEMP, DOOR SWITCH, EXT ALARM, SYSTEM OFF, LIGHT

SWITCH, CAMERA SWITCH

DISABLED

DIG IN 3 STATE

Sets whether the switch activates when opened or closed

OPEN, CLOSED

CLOSED

2ND ROOM TEMP

If DIG IN (1, 2 and/or 3) MODE = 2ND ROOM TEMP: This value becomes the ROOM TEMP setpoint when the digital input is active

-50°F to 90°F

-50°F

SUCT PRES OFFSET

An offset added or subtracted from the suction line pressure transducer reading to calibrate, if needed

-5.0 to 5.0 psig

0.0 psig

SUCT TEMP OFFSET

An offset added or subtracted from the suction temperature sensor reading to calibrate, if needed

-5.0°F to 5.0°F

0.0°F

AIR TEMP OFFSET

An offset added or subtracted from the room temperature sensor reading to calibrate, if needed

-5.0°F to 5.0°F

0.0°F

COIL TEMP OFFSET

An offset added or subtracted from the coil temperature sensor reading to calibrate, if needed

-5.0°F to 5.0°F

0.0°F

AUX TEMP OFFSET

An offset added or subtracted from the auxiliary temperature sensor reading to calibrate, if needed

-5.0°F to 5.0°F

0.0°F

TEMP UNITS

Units for temperature’s display in °F or °C

FAHRENHEIT/CELSIUS

FAHRENHEIT

AIR TEMP DIFF

The number of degrees above ROOM TEMP before the controller will go into REFRIGERATION mode

0°F to 25°F

1°F

EXTREME TEMP DIFF

ADVANCED TOPIC: Call KE2 Therm for assistance

Setpoints Menu

14

01/13 Rev. A 151627