Ke2 evaporator efficiency, Setpoints menu, Parameter name description range default current – Nor-Lake Enviro-Control IOM User Manual
Page 14: Installation instructions, Enviro-control
KE2 EvaporatorEfficiency
Installation Instructions
Parameter Name
Description
Range
Default
Current
ROOM TEMP
Room temperature to be maintained
-50°F to 90°F
-10°F
DEFROST TYPE
Method of defrost used on the evaporator coil: Electric, Air, Hot Gas with Liquid Line Solenoid/Compressor relay off, Hot Gas with
Liquid Line Solenoid/compressor relay on
ELEC, AIR, HOT GAS COMP ON, HOT GAS COMP OFF
ELEC
VALVE TYPE
Type of valve used on the system: mechanical, pre-configured electric, custom EEV configuration
MECHANICAL, KE2, SER/SEI 1 TO 20, SER B TO L, SEI 30, SEI 50, SEH, ETS12 TO 50,
ETS100, ETS250/400, KV, CAREL, CUSTOM;
MECHANICAL
Cust
om
EE
V O
nly
MOTOR TYPE
If VALVE TYPE = CUSTOM: The motor type used in the valve
BIPOLAR, UNIPOLAR
BIPOLAR
MOTOR STEP RATE
If VALVE TYPE = CUSTOM: The motor speed setting in number of steps per second
30 to 400 steps/second
200 steps
MAX VALVE STEPS
If VALVE TYPE = CUSTOM: The total number of steps required to move the valve from closed to fully open
200 to 6400 steps
1600 steps
SUPERHEAT
The superheat value that the controller will maintain, (not applicable if VALVE TYPE = MECHANICAL)
5°F to 30°F
8°F
MAX OPERATING PRES
The maximum allowable suction pressure, (not applicable if VALVE TYPE = MECHANICAL)
10 to 150 psig
150 psig
REFRIGERANT
The type of refrigerant used in the refrigeration system
404A, R507, 407A, 407C, 422A, 422D, 134A, R22, R717, 438A, 408A, 409A, 410A,
404A
AUX TEMP MODE
Configuration mode of the auxiliary temperature sensor
DISABLED, MONITOR, 2ND AIR TEMP, 2ND COIL TEMP
DISABLED
AUX RELAY MODE
Configuration mode of the auxiliary relay.
ALARM RELAY, 2 SPEED FAN CTL, 2ND COMP RELAY, 2ND FAN RELAY, 2ND DEFR
RELAY, LIGHT RELAY, CAMERA RELAY
ALARM RELAY
MIN COMP RUN TIME
Minimum amount of time the liquid line solenoid/compressor relay must remain on after it is energized
0 to 15 minutes
2 minutes
MIN COMP OFF TIME
Minimum amount of time the liquid line solenoid/compressor relay must remain off before it can be energized again.
0 to 15 minutes
5 minutes
REFRIG FAN MODE
Fan operation while in refrigeration mode
ON WITH COMPRESSOR, PERMANENT, CYCLE
ON WITH COMPRESSOR
DEFROST MODE
The method the controller uses to determine when to initiate a defrost.
DEMAND, SCHEDULED, RUN TIME
DEMAND
DEFROSTS / DAY
If DEFROST MODE = SCHEDULED: The number of evenly spaced defrosts per day the controller will initiate.
0 to 8
5
1ST DEFROST DELAY
If DEFROST MODE = SCHEDULED: The amount of time from controller power up until the first defrost is initiated.
0 to 240 minutes
120 minutes
DEFROST FAN STATE
Whether or not to run the evaporator fans during defrost
ON/OFF
OFF if DEFROST TYPE = ELEC, HOT GAS COMP ON, HOT GAS COMP OFF
ON if DEFROST TYPE = AIR
DEFROST TERM TEMP
The temperature the coil sensor(s) must exceed in order to terminate defrost. The defrost relay is de-energized at this point.
35°F to 90°F
50°F if DEFROST TYPE = ELEC, HOT GAS COMP ON, HOT GAS COMP OFF
40°F if DEFROST TYPE = AIR
DEFROST PARAMETER
The maximum amount of time the defrost relay will be energized.
0 to 90 minutes
25 minutes if DEFROST TYPE = ELEC
10 minutes if DEFROST TYPE = HOT GAS COMP ON, HOT GAS COMP OFF
40 minutes if DEFROST TYPE = AIR
DRAIN TIME
Time to be in drain mode (drip time)
0 to 15 minutes
2 minutes
COMP RUN TIME
If DEFROST MODE = RUN TIME: The amount of time liquid line solenoid/compressor relay is energized before the next defrost is initiated.
0 to 24 hours
6 hours
ELEC DEFROST MODE
If DEFROST TYPE = ELEC: Whether to leave the defrost relay energized during the defrost cycle or to utilize advanced defrost algorithm.
PULSE, PERMANENT
PULSE
FAN DELAY TEMP
After defrost, the coil sensor reading must fall below this temperature set point in order for the controller to resume normal fan operation.
-40°F to 35°F
20°F
MAX FAN DELAY TIME
Maximum amount of time after defrost to resume normal fan operation.
0 to 20 minutes
2 minutes
PUMP DOWN TIME
Minimum amount of time between de-energizing the liquid line solenoid/compressor relay and energizing the defrost relay.
0 to 10 minutes
0 minutes
MULTI AIR TEMP CTRL
Select control method to use with multiple room temperature sensors
AVERAGE, WARMEST
WARMEST
Bonded Con
tr
ol-
lers O
nly MULTI EVAP COOL
Select type of multi evaporator control - options are synchronous or independent
SYNC, INDEPENDENT
SYNC
MULTI EVAP DEFROST
Select whether to have all bonded controllers initiate defrost mode at the same time or independently.
SYNC, INDEPENDENT
SYNC
MULTI EVAP SENSOR
Select whether or not to share room temperature, coil temperature and suction pressure sensor data with bonded controllers.
SHARED, NOT SHARED
SHARED
HIGH TEMP ALARM OFFSET
The number of degrees above ROOM TEMP for a HIGH TEMP ALARM condition.
0°F to 99.9°F
10°F
HIGH TEMP ALARM DELAY
Minutes the room temperature must remain above ROOM TEMP + HIGH TEMP ALARM OFFSET before issuing a HIGH TEMP ALARM
0 to 120 minutes
60 minutes
LOW TEMP ALARM OFFSET
The number of degrees below ROOM TEMP for a LOW TEMP ALARM condition.
0°F to 20°F
4°F
LOW TEMP ALARM DELAY
Minutes the room temperature must remain below ROOM TEMP - LOW TEMP ALARM OFFSET before issuing a LOW TEMP ALARM
0 to 30 minutes
10 minutes
DOOR ALARM DELAY
If DIG IN (1, 2 and/or 3) MODE = DOOR SWITCH: The amount of time, in minutes, before an alarm condition is initiated if door is open and room
temperature is 5 degrees above ROOM TEMP + AIR TEMP DIFF
0 to 180 minutes
30 minutes
DIG IN 1 MODE
Sets the function of the digital input
DISABLED, 2ND ROOM TEMP, DOOR SWITCH, EXT ALARM, SYSTEM OFF
DOOR
DIG IN 1 STATE
Sets whether the switch activates when opened or closed
OPEN, CLOSED
CLOSED
DIG IN 2 MODE
Sets the function of the digital input
DISABLED, 2ND ROOM TEMP, DOOR SWITCH, EXT ALARM, SYSTEM OFF
DISABLED
DIG IN 2 STATE
Sets whether the switch activates when opened or closed
OPEN, CLOSED
CLOSED
DIG IN 3 MODE
Sets the function of the digital input
DISABLED, 2ND ROOM TEMP, DOOR SWITCH, EXT ALARM, SYSTEM OFF, LIGHT
SWITCH, CAMERA SWITCH
DISABLED
DIG IN 3 STATE
Sets whether the switch activates when opened or closed
OPEN, CLOSED
CLOSED
2ND ROOM TEMP
If DIG IN (1, 2 and/or 3) MODE = 2ND ROOM TEMP: This value becomes the ROOM TEMP setpoint when the digital input is active
-50°F to 90°F
-50°F
SUCT PRES OFFSET
An offset added or subtracted from the suction line pressure transducer reading to calibrate, if needed
-5.0 to 5.0 psig
0.0 psig
SUCT TEMP OFFSET
An offset added or subtracted from the suction temperature sensor reading to calibrate, if needed
-5.0°F to 5.0°F
0.0°F
AIR TEMP OFFSET
An offset added or subtracted from the room temperature sensor reading to calibrate, if needed
-5.0°F to 5.0°F
0.0°F
COIL TEMP OFFSET
An offset added or subtracted from the coil temperature sensor reading to calibrate, if needed
-5.0°F to 5.0°F
0.0°F
AUX TEMP OFFSET
An offset added or subtracted from the auxiliary temperature sensor reading to calibrate, if needed
-5.0°F to 5.0°F
0.0°F
TEMP UNITS
Units for temperature’s display in °F or °C
FAHRENHEIT/CELSIUS
FAHRENHEIT
AIR TEMP DIFF
The number of degrees above ROOM TEMP before the controller will go into REFRIGERATION mode
0°F to 25°F
1°F
EXTREME TEMP DIFF
ADVANCED TOPIC: Call KE2 Therm for assistance
Setpoints Menu
14
01/13 Rev. A 151627
Enviro-Control™