Enviro-Control™ Factory Default Settings
Electric Defrost Factory Settings
(freezer applications)
Air Defrost Factory Settings
(cooler applications)
PARAMETER
SETTING
PARAMETER
SETTING
ROOM TEMP
-10.0°F
ROOM TEMP
36.0°F
DEFROST TYPE
ELEC
DEFROST TYPE
AIR
VALVE TYPE
CUSTOM
VALVE TYPE
CUSTOM
MOTOR TYPE
BIPOLAR
MOTOR TYPE
BIPOLAR
MOTOR STEP RATE
50 steps/sec
MOTOR STEP RATE
50 steps/sec
MAX VALVE STEPS
480 steps
MAX VALVE STEPS
480 steps
SUPER HEAT
8°F
SUPER HEAT
8°F
MAX OPERATING PRESSURE
150 psig
MAX OPERATING PRESSURE 150 psig
REFRIGERANT 404A
REFRIGERANT
404A
AUX TEMP MODE
2ND COIL TEMP
AUX TEMP MODE
2ND COIL TEMP
AUX RELAY MODE
ALARM RELAY
AUX RELAY MODE
ALARM RELAY
MIN COMP RUN TIME
2 minutes
MIN COMP RUN TIME
2 minutes
MIN COMP OFF TIME
5 minutes
MIN COMP OFF TIME
5 minutes
REFRIG FAN MODE
ON WITH
COMPRESSOR
REFRIG FAN MODE
ON WITH
COMPRESSOR
DEFROST MODE
DEMAND
DEFROST MODE
DEMAND
DEFROSTS / DAY
5
DEFROSTS / DAY
5
1ST DEFROST DELAY
120 minutes
1ST DEFROST DELAY
120 minutes
DEFROST FAN STATE
OFF
DEFROST FAN STATE
ON
DEFROST TERM TEMP
50°F
DEFROST TERM TEMP
50°F
DEFROST PARAMETER
25 minutes
DEFROST PARAMETER
15 minutes
DRAIN TIME
2 minutes
DRAIN TIME
2 minutes
COMP RUN TIME
6 hours
COMP RUN TIME
6 hours
ELEC DEFROST MODE
PULSE
ELEC DEFROST MODE
PULSE
FAN DELAY TEMP
20°F
FAN DELAY TEMP
20°F
MAX FAN DELAY TIME
2 minutes
MAX FAN DELAY TIME
2 minutes
PUMP DOWN TIME
2 minutes
PUMP DOWN TIME
2 minutes
MULTI AIR TEMP CTRL
WARMEST
MULTI AIR TEMP CTRL
WARMEST
HIGH TEMP ALARM OFFSET
10°F
HIGH TEMP ALARM OFFSET
10°F
HIGH TEMP ALARM DELAY
60 minutes
HIGH TEMP ALARM DELAY
60 minutes
LOW TEMP ALARM OFFSET
4°F
LOW TEMP ALARM OFFSET
4°F
LOW TEMP ALARM DELAY
10 minutes
LOW TEMP ALARM DELAY
10 minutes
DOOR ALARM DELAY
30 minutes
DOOR ALARM DELAY
30 minutes
DIG IN 1 MODE
DOOR
DIG IN 1 MODE
DOOR
DIG IN 1 STATE
CLOSED
DIG IN 1 STATE
CLOSED
DIG IN 2 MODE
DISABLED
DIG IN 2 MODE
DISABLED
DIG IN 2 STATE
CLOSED
DIG IN 2 STATE
CLOSED
DIG IN 3 MODE
DISABLED
DIG IN 3 MODE
DISABLED
DIG IN 3 STATE
CLOSED
DIG IN 3 STATE
CLOSED
2ND ROOM TEMP
-50°F
2ND ROOM TEMP
-50°F
SUCT PRES OFFSET
0.0 psig
SUCT PRES OFFSET
0.0 psig
SUCT TEMP PFFSET
0.0°F
SUCT TEMP PFFSET
0.0°F
AIR TEMP OFFSET
0.0°F
AIR TEMP OFFSET
0.0°F
COIL TEMP OFFSET
0.0°F
COIL TEMP OFFSET
0.0°F
AUX TEMP OFFSET
0.0°F
AUX TEMP OFFSET
0.0°F
TEMP UNITS
FAHRENHEIT
TEMP UNITS
FAHRENHEIT
AIR TEMP DIFF
1°F
AIR TEMP DIFF
1°F