KE2 EvaporatorEfficiency

Installation Instructions

Controller

Input Voltage:

120V or 208 - 240V

Ambient Temp:

-40° to 140°F

Operating Temp:

-40° to 140°F

Display:

4-digit alphanumeric LED

IP Rating:

IP65

Inputs:

(4) temperature sensors (KE2 SKU 20200)
(1) pressure transducer (KE2 SKU 20204)

Valve Types:

unipolar and bipolar stepper motors (12V)
(Beacon® is 21V)

Relays:

20A resistive (defrost)
10A inductive (evaporator fan)
(2) 3A inductive rated cycles

Digital Input 1 & 2:

door contact, use 2nd air temp setpoint, disabled,

system off, external alarm notification

Digital Input 3

door contact, use 2nd air temp setpoint, dis-

abled, system off, external alarm notification,

lights, camera

Communication:

Standard TCP/IP

Pressure Transducer

Pressure Range:

0 to 150 psia

Proof Pressure:

450 psi

Burst Pressure:

1500 psi

Operating Temp:

-40° to 275°F

Temperature Sensor

Sensor Specs:

-60° to 150°F moisture resistant package

Communication

The KE2 Evap uses standard TCP/IP communication. The con-

troller is equipped with an RJ-45 female connector to connect

to Ethernet cable.

To communicate with the controller, the user will use a web

browser to see the KE2 MasterView. The information is stored

on the controller, so special software is not required.

A standard Ethernet cable should be used between the periph-

eral device and the controller. One end is connected to the

controller, and the other to the Ethernet port on the PC or Mas-

terView. The Ethernet port will look similar to a telephone jack.

The difference is the Ethernet port is larger with 8 wires instead

of 6.

In installations where multiple evaporators are piped to a single

condenser, networking the controllers is required. This prevents

damage to the system by synchronizing the defrost cycles. Net-

worked controllers have an additional safety layer to protect the

system. When networked, the controllers share information,

such as air temperature, to allow a controller in alarm mode to

continue to provide refrigeration until the system is serviced.

When networking multiple controllers an ethernet switch or

router is required. KE2 Network Router is available in a 4-port

and KE2 Switch in an 8-port model. The KE2 Router includes

wireless access. The 8-port switch should be used for larger

networks. Multiple switches can be ganged together to cre-

ate additional ports for the network. When necessary, the lo-

cal Network Adminstrator should be contacted to facilitate the

network installation.

Table 4 - Defrost Defaults

Setpoint

Electric

Air

Hot Gas

Defost Fan State:

Off

On

Off

Defrost Termination

Temperature

Setpoint:

50

40

50

Maximum Defrost

Time

30

45

15

Electric Defrost

Mode:

Pulse

Permanent

Permanent

Table 5 - Ethernet Specifications Summary

Specifications

Ethernet -

Unshielded Twisted Pair

(UTP)

Topology

star

Network Friendly

YES

Maximum Cable Length

330 feet (copper)

Maximum Data Rate

1,000 mbs

Native Internet

YES

Supported Devices

thousands

Response Time

milliseconds

For additional information on Ethernet Cable, consult IEEE 802.