Lyntec RPCM User Manual
Page 35

139-0498-01.35
35
Appendix C
Auxiliary Power Supply
24 Vdc (200mA maximum Current)
Communication Interface
RJ-45 (8P8C) TCP/IP/sACN/Web
Server/100 Base TX
DMX in/thru 5-wire
Circuit breaker delay
0.025 sec to 8 min (selectable)
Environmental Standards
Operating Temperature: –5°C
to +65°C (internal panelboard
temperature)
Storage Temperature: –20°C to 85°C
Operating Humidity: 5% to 95%
Time Clock
Operation during absence of power
= >2 years
Memory Retention
Program: > 20 years
Standards
UL1640 CSA 2.22-10
ESD Immunity
IEC 1000, Level 4
RF Susceptibility
IEC 1000, Level 3
Electrical Fast Transient
Susceptibility
IEC 1000, Level 3
Electrical Surge Suceptibility--power
line
IEC 1000, Level 4
Electrical Surge Suceptibility--data
line
IEC 1000, Level 3
FCC--Part 15, Class A
ETL Tested to: CU 2.22-10 and UL1640
Specifi cations