American Power Conversion VS 50 User Manual

Page 47

background image

Magnum VS –48 Vdc User Manual

Page 47

ALARM/

[MENU LOCATION]

DESCRIPTION DEFAULT

SETTINGS

System LT Alm
[System/DC Parameters]

The System Temperature is below the
System Low Temperature threshold. Not
the same as battery temperature alarm.

Minor

Low Voltage Alarm
[Power Modules/Rectifiers]

The System Voltage is below the System
Low Voltage threshold. Not the same as
battery voltage alarm.

Minor

LVD Alarm
[Batteries/LVD]

The controller opened the LVD. If unit
has a battery LVD, no power will be
available to turn on any Output Relays.

Major

User Output Relay 1 Alarm
[I/O/Output]

Output Relay 1 Alarm can be “mapped”
to activate other output relays (“Ignore”
activates no additional relays).

Ignore

Rectifier 1-of-N Alm
[Power Modules/Rectifiers]

Rectifier Fail 1-of-N alarm occurs. This is
a special rectifier alarm group that
signifies that one rectifier has at least
one alarm condition.

Minor

Rectifier 2-of-N Alm
[Power Modules/Rectifiers]

Rectifier Fail 2-of-N alarm occurs This is
a special rectifier alarm group that
signifies that more than one rectifier has
at least one alarm condition.

Major

Rectifier Current Limit Alarm
[Power Modules/Rectifiers]

A rectifier is in the current limited mode.

n of N

Rectifier Fan Fail Alm
[Power Modules/Rectifiers]

A rectifier fan has failed.

n of N

Rectifier RFA Alarm
[Power Modules/Rectifiers]

A rectifier output has failed.

n of N