beautypg.com

American Power Conversion VS 50 User Manual

Page 43

background image

Magnum VS –48 Vdc User Manual

Page 43

Battery Visual and Safety Inspection

Check that the battery temperature probe is firmly attached to the battery.
Check the mechanical integrity of the battery framing, racking, or cabinet. Tighten where necessary.
If there is a battery disconnect device fitted, ensure that it is properly connected and protected.

1. Check the general appearance and cleanliness of the battery. Clean if necessary. Use only approved

cleaning materials.

Visually inspect each cell for the following, and clean and neutralize if necessary. Document discrepancies on Site
form accordingly.

a. Cracks.
b. Case

leaks.

c. Post-seal

leaks.

d. Pressure relief valve leaks (VRLA only).
e. Case swelling (VRLA only).
f. Terminal corrosion and connector corrosion.

2. Check the torque of all battery inter-cell connector in accordance with specifications. Re-torque if

necessary (annual only).

3. Measure and record ambient temperature.

6.3. Test

System Voltage Test

1. Verify with a voltmeter directly attached to the dc bus that the system voltage is correct.
2. System voltage should also agree with the battery float voltage set up in the battery parameters section.

Be sure to take into account the effects of temperature compensation and battery recharge current limit.


Rectifier Current Share Test


Verify that the highest rectifier current and the lowest current are within 5 A of each other.

System Current Test


Verify the System current equal to the total of the rectifier currents. System current should equal the total current of
the loads as well as any battery current.

Rectifier Alarm Test


1. Verify that all of the rectifiers report RFA Alarm is off.
2. Remove 1 rectifier and verify that you get a Minor alarm for Rect 1 of n failure on the controller and the

customer remote alarm panel.

3. Remove the second rectifier and verify that you get a Major alarm for Rect 2 of n failure on the controller

and the customer remote alarm panel.

4. After the fan has completely stopped spinning, insert a plastic pen or plastic screwdriver into the fan blade

of one of the rectifiers and reinsert both rectifiers

5. Verify that you get the fan fail alarm on controller and the customer remote alarm panel.
6. Remove the fan fail device.

System Temperature Test


Verify that the system temperature is correct.

This manual is related to the following products: