Page 56

Appendix E. NL100 to MD485 Network
b. IPPort – Internet IP Address – NL100 IP address : NL100 RS-485
serial server port number. (The NL100 RS-485 serial server port
number is configured using the NL100 configuration menu.)
c. PakBus Port – defaults (PakBus dataloggers only)
d. CR1000 – default settings, schedule collections as desired
MD485 Configuration
1) Active Ports – “CS I/O and RS-485”
2) Communication Mode – “Transparent Communication”
3) CS I/O Port Configuration – Modem Enable
4) RS-485 Port Configuration – Desired baud rate
NL100 Configuration
1) RS-485 config – “TcpSer”
2) RS-485 bps – Desired baud rate
3) RS-485 serial server port number – May be left at default, but must
match what is entered in LoggerNet Setup
4) Ethernet 10BaseT – “enabled”
5) 10BaseT port IP address – NL100 IP address
6) 10BaseT port network mask– NL100 network mask
The other NL100 options can be left in their default state.