Model HMP45C Temperature and Relative Humidity Probe

SatVP(e_Sat,

AirTC)

'Compute Vapor Pressure, RH must be a fraction

e_kPa = e_Sat * RH_Frac

CallTable(Temp_RH)
NextScan
EndProg

CR10(X) Program that Computes Vapor Pressure and Saturation Vapor Pressure

;Turn the HMP45C on.
;
01: Do (P86)
1: 41

Set Port 1 High

;Jumper wire from SW12V control to C1

;Orange wire (C1) if older wiring

;Green wire (C1) if using SW12V device

;For CR23X or CR5000 use 49 for SW12V internal

;control

port


;Pause 150 mSec before making measurements so the
;probe can stabilize on true readings.
;
02: Excitation with Delay (P22)
1: 1

Ex

Channel

2: 0

Delay W/Ex (units = 0.01 sec)

3: 15

Delay After Ex (units = 0.01 sec)

4: 0

mV

Excitation


;Measure the HMP45C temperature.
;
03: Volt (SE) (P1)
1: 1

Reps

2: 5

2500 mV Slow Range

;CR510, CR500 (2500mv); CR23X (1000 mV);

21X, CR7 (5000 mV)

3: 3

SE

Channel

;Yellow wire (SE 3), white or purple wire (AG)

4: 1

Loc [ T_C ]

5: .1

Mult

6: -40

Offset


;Measure the HMP45C relative humidity.
;
04: Volt (SE) (P1)
1: 1

Reps

2: 5

2500 mV Slow Range

;CR510, CR500 (2500mv); CR23X (1000 mV);

21X, CR7 (5000 mV)

3: 4

SE

Channel

;Blue wire (SE 4), white or purple wire (AG)

4: 2

Loc [ RH_frac ]

5: .001

Mult

6: 0

Offset