beautypg.com

Calibration, Maintenance – Campbell Scientific 03002, 03101, and 03301 R. M. Young Wind Sentry Sensors User Manual

Page 35

background image

Page 2

03002-5-90(D)

FAILURE TO PROPERLY GROUND THE WIND SENTRY

MAY RESULT IN ERRONEOUS SIGNALS

OR TRANSDUCER DAMAGE.

Grounding the Wind Sentry is vitally important. Without proper grounding,

static electrical charge can build up during certain atmospheric conditions

and discharge through the transducers. This discharge can cause

erroneous signals or transducer failure. To direct the discharge away

from the transducers, the instrument is made with a special anti-static

plastic. It is very important that the instrument be connected to a good

earth ground. There are two ways this may be accomplished. First,

the Wind Sentry may be mounted on a metal pipe which is connected

to earth ground. The mounting pipe should not be painted where the

Wind Sentry is mounted. Towers or masts set in concrete should be

connected to one or more grounding rods. If it is difficult to ground the

mounting post in this manner, the following method should be used.

Inside the junction box the terminal labeled EARTH GND is internally

connected to the anti-static housings. This terminal should be connected

to an earth ground (Refer to wiring diagram).

Initial installation is most easily done with two people; one to adjust

the instrument position and the other to observe the indicating device.

When anemometer and vane are mounted on the same cross arm

(Model 03002), the azimuth potentiometer has been aligned at the

factory such that the mounting cross arm should be oriented North-

South with the vane on the North end.

To install the Wind Sentry, follow these steps:

1. MOUNT WIND SENTRY

a) Connect sensor cable to Wind Sentry junction box.

b) Place Wind Sentry on mounting post. Do Not tighten

band clamp yet.

c) Connect sensor cable to indicator.

2. ALIGN VANE

a) Select a known azimuth reference point on the horizon.

b) Sighting down vane centerline, point counterweight at

reference point on horizon.

c) While holding vane in position, slowly turn base until

indicator displays proper value.

d) Tighten mounting post band clamp.

CALIBRATION

The Wind Sentry is fully calibrated before shipment and should

require no adjustments. Recalibration may be necessary after some

maintenance operations. Periodic calibration checks are desirable

and may be necessary where the instrument is used in programs

which require auditing of sensor performance.

For wind direction calibration, the following method can yield an

accuracy of ±5° or better if carefully done. Begin by connecting

the instrument to a signal conditioning circuit which indicates wind

direction value. This may be an indicator which displays wind direction

values in angular degrees or simply a voltmeter monitoring the output.

Hold or mount the instrument so the vane center of rotation is over

the center of a sheet of paper which has 30° or 45° crossmarkings.

Position the instrument so the mounting crossarm is oriented north-

south with the vane on the north and the anemometer on the south.

With the counterweight pointing directly at the anemometer the wind

direction signal should correspond to 180° or due south. Looking from

above, visually align the vane with each of the crossmarkings and

observe the indicator display. It should correspond to vane position

within 5°. If not, it may be necessary to adjust the relative position of

the vane skirt and shaft. See step 3 in the MAINTENANCE section

under potentiometer replacement.

It is important to note that while the sensor mechanically rotates

through 360°, the full scale wind direction signal from the signal

conditioning occurs at 352°. For example, in a circuit where 0 to

1.00 VDC represents 0° to 360°, the output must be adjusted for

0.978 VDC when the instrument is at 352° full scale. (352°/360° X

1.00 volts = 0.978 volts)

Wind speed calibration is determined by the cup wheel turning factor

and the output characteristics of the transducer. Calibration formulas

showing cup wheel rpm and frequency output vs. wind speed are

included below.

To calibrate wind system electronics using an actual signal from

the instrument, temporarily remove the cup wheel and connect an

Anemometer Drive to the cup wheel shaft. Calculate wind speed by

applying the appropriate calibration formula to the motor rpm and

adjust the signal conditioning electronics for proper value. For example,

with the cup wheel shaft turning at 1800 rpm, adjust the indicator to

display 22.7 meters per second. ([(0.01250 X 1800) + 0.2] = 22.7)

CALIBRATION FORMULAS

Model 03102 Wind Sentry Anemometer

WIND SPEED vs CUP WHEEL RPM

m/s

=

(0.01250 x rpm) + 0.2

knots =

(0.02427 x rpm) + 0.4

mph

=

(0.02795 x rpm) + 0.4

km/hr =

(0.04499 x rpm) + 0.7

WIND SPEED vs OUTPUT FREQUENCY - Hz

m/s

=

(0.7500 x Hz) + 0.2

knots =

(1.4562 x Hz) + 0.4

mph

=

(1.6770 x Hz) + 0.4

km/hr =

(2.6994 x Hz) + 0.7

MAINTENANCE

Given proper care, the Wind Sentry should provide years of service.

Because of its durable, corrosion resistant construction, the instrument

requires little maintenance. The only components likely to require

replacement due to normal wear are the precision ball bearings and

the azimuth potentiometer. Replacement of these components should

only be performed by a qualified instrument technician. If service

facilities are not available, return the instrument to the factory. Refer

to the accompanying drawings to become familiar with part names

and locations. Maximum torque on all set screws is 80 oz-in.

POTENTIOMETER REPLACEMENT

The potentiometer has a life expectancy of fifty million revolutions.

As it becomes worn, the element may produce noisy signals or

become non-linear. When the signal noise or non-linearity become

unacceptable, replace the potentiometer as follows:

1. REMOVE POTENTIOMETER

a) Remove three screws which secure upper and lower

sections of main housing.

b) Carefully remove upper housing exposing wiring connections

to circuit board.

c) Unsolder potentiometer wires from circuit board.

Note color coding.

d) Using a knife blade or similar instrument, loosen

potentiometer assembly from upper housing and slide it out.

2. INSTALL NEW POTENTIOMETER

a) Slide new potentiometer cell into upper housing. Be sure to

engage cell key into housing notch.

b) Solder potentiometer wires to circuit board.

Observe color code.

c) Join two sections of main housing. Secure with screws

removed in step 1a.