Preparing the poly panels and h-channels – Chatsworth Products Hot Aisle Containment User Manual
Page 41
Aisle Containment Manual, Rev. 2.0
___
June 2013
Chatsworth Products
41
PREPARING THE POLY PANELS AND H-CHANNELS:
1. The ribs of the double wall poly panels are oriented in a vertical direction. For each cabinet
height, cut the vertical dimension of the panels to be equal to the cabinet to ceiling distance
less approximately
6”. Cut using a sharp knife and a straight edge. For best results, use
specialized cutting tools like the Guardian Knife Guide and Coro-
Claw™ by Saw Trax Mfg.
Inc., to cut across or with the ribs respectively.
2. After cutting, remove protective film from both sides of the plastic panel.
3. Plastic H-channels are used to join adjacent poly panels that are not connected with the
lateral brace accessory. The H-channels should be cut to the cabinet to ceiling distance
less approximately 13 inches. The plastic H-channels are saw cut.
H-CHANNELS