1 gsm modem settings – sms configuration, Gsm modem settings – sms configuration – Horner APG XLt OCS HE-GSM04 User Manual
Page 28

PAGE 28
GPRS / GSM MODEM Configuration
MAN4005-04-EN
5.2.1
GSM Modem Settings – SMS Configuration
•
In this example, the screen is already configured. The SMS Configuration screen has several sections that require
configuration.
Status Register Settings
Address
Enter the starting register location to indicate the status of the SMS communication. This is a block of four
registers that are consecutive in memory. For example, if you are using R31– R34, you need to enter the
starting register address as %R0031.
Name
Enter (or select) an I/O Name.
The Status Register contains a status bit indicating the condition of the SMS communication. The following table contains the
meaning of each status bit…
Status Bits
SMS Status Bits
Description
Bit 13
Receive response failed
Set within 10 seconds if Read SMS command fails
Bit 14
Initialization Failed
Set after 1 min of entering into RUN mode if Modem
initialization fails
Bit 15
Transmit Failed
Set within 10 seconds if SMS Transmit fails
Bit 16
Communication Failed
Set within 10 seconds if communication with modem fails
Bit 17 - Bit 24
Bit Error Rate value.
Updated within 30 sec after entering into RUN mode
Bit 25 – Bit 32
Receive level value.
Updated within 30 sec after entering into RUN mode
Bit 33 - Bit 48
Invalid message count
Count is incremented whenever a message is received from
not configured sender or in not configured message format.
Bit 49 - Bit 56
Send/Receive retry count
Incremented every time when send / Receive of SMS fails. It
is incremented within 10 seconds if Send / Receive failure.
Bit 57 – Bit 64
Re-initialization count
This count is incremented whenever modem initialization
fails. The modem re-initializes itself if the send / receive
command fails for 10 consecutive times.
Page 28 of 62 ECN # 956