beautypg.com

Ashcroft GC35 - Pressure Sensor User Manual

Page 7

background image

7

1

4

2

3

NPN Type Switch Function (Wiring to Relay)

GC35

Red

Relay output

Electric current resistor

Photo coupler

Open collector
output

Relay

(OUT1)

30Vdc/80mA max.

NOTE: Confirm the relay’s rated current and voltage are within the transistors rating.

Relay protective transistor
diode (make sure to install)

(OUT2)

Power (+)

Power (−)

Black

White

Green

1

4

2

3

NPN Type Switch Function (Wiring to Photo Coupler)

GC35

Red

(OUT1)

30Vdc/80mA max.

(OUT2)

Power (+)

Power (−)

Black

White

Green

1

4

2

3

NPN Type Switch Function (Voltage Output)

GC35

Red

(OUT1)

30Vdc/80mA max.

(OUT2)

Power (+)

Power (−)

Black

White

Green

Voltage HL

(H/L)

Pin 611C175

Cable

Wiring Color

RED

WHITE

GREEN

BLACK

WIRING

PIN OUT

TERMINAL NUMBER

1

3

2

4

1

2

3

4

2 Switch

1 Switch

(No 4-20mA)

Analog Output

Power (+)

Power (+)

OUT2

Analog (+) Output

Power (–)

Power (–)

OUT1

OUT1

NOTE: Mount M12 connector pins face on with electrical mating cable.

Do NOT turn or pull on connector to prevent damage to unit.

Cable Color
Red

Power (+)

Black

Open Collector Output OUT 1

White

Open Collector Output OUT 2 / analog output

Green

Power (−)

Silver

Shielded Ground

Clear

Vent Tube

4. WIRING: