14. TROUBLESHOOTING

Error

Possible cause

Actions

Press any key to turn indication on or

No display

Energy-saving mode

disable power-saving mode in the setup.

(Function setting mode)

Ǟ

(Power-save setting)

Wiring

Carry out wire connection correctly according to

Supply voltage

the connection point.

Setting of comparator

Set a comparator output type (NPN, PNP)

output type to match the setup of apparatus.

No output

(Function setting mode)

Ǟ

(Comparator operation selection)

Comparator enabled

Enable a comparator in the setup.

(Comparator setting mode)

Ǟ

(Comparator Use/No use)

Display/output do

Pressure leak

Check pressure connection and piping.

not indicate when

Verify applied pressure by using a pressure gauge

pressure is applied

Too low pressure applied

with the suitable pressure range.

(remains at zero)

Zero point shift

Perform zero point adjustment

(zero point adjustment mode)

Pressure indication mode Select a pressure indication

(Function setting mode)

Ǟ

(Display setting)

Analog scaling mode

Check analog output scaling setup

Unit display/output

(Function setting mode)

Ǟ

(Analog Output Scaling)

conflicts with the

Check the operational mode of the comparator, a

value of applied

Set value of the

preset value, and the preset value of delay time.

pressure

comparator output

(Function setting mode)

Ǟ (

Select comparator mode)

(Comparator setting mode)

Ǟ (

Comparator setting point)

(Comparator setting mode )

Ǟ (

Comparator delay)

Overloaded comparator

Use unit with a load current set to 80mAdc or lower.

Foreign material

Clean / remove obstruction in piping

(blockage)

17

Error
Display

Contents

Actions

Out of pressure display range (Upper limit)

FFF

A pressure above 110% FS of pressure

range is applied, or when indicated value
exceeds 1999.

Adjust the applied pressure

Out of pressure display range (Lower limit)

within the rated pressure.

FFF

A pressure less than –10% FS of pressure
range is applied, or when indicated value
falls below –1999.

E-0

During zero point adjustment, applied

Open the unit to the atmos-

pressure is outside the range of ±10% FS

phere and perform zero
point adjustment again.