14. TROUBLESHOOTING
Error
Possible cause
Actions
Press any key to turn indication on or
No display
Energy-saving mode
disable power-saving mode in the setup.
(Function setting mode)
Ǟ
(Power-save setting)
Wiring
Carry out wire connection correctly according to
Supply voltage
the connection point.
Setting of comparator
Set a comparator output type (NPN, PNP)
output type to match the setup of apparatus.
No output
(Function setting mode)
Ǟ
(Comparator operation selection)
Comparator enabled
Enable a comparator in the setup.
(Comparator setting mode)
Ǟ
(Comparator Use/No use)
Display/output do
Pressure leak
Check pressure connection and piping.
not indicate when
Verify applied pressure by using a pressure gauge
pressure is applied
Too low pressure applied
with the suitable pressure range.
(remains at zero)
Zero point shift
Perform zero point adjustment
(zero point adjustment mode)
Pressure indication mode Select a pressure indication
(Function setting mode)
Ǟ
(Display setting)
Analog scaling mode
Check analog output scaling setup
Unit display/output
(Function setting mode)
Ǟ
(Analog Output Scaling)
conflicts with the
Check the operational mode of the comparator, a
value of applied
Set value of the
preset value, and the preset value of delay time.
pressure
comparator output
(Function setting mode)
Ǟ (
Select comparator mode)
(Comparator setting mode)
Ǟ (
Comparator setting point)
(Comparator setting mode )
Ǟ (
Comparator delay)
Overloaded comparator
Use unit with a load current set to 80mAdc or lower.
Foreign material
Clean / remove obstruction in piping
(blockage)
17
Error
Display
Contents
Actions
Out of pressure display range (Upper limit)
Ⅺ
FFF
A pressure above 110% FS of pressure
range is applied, or when indicated value
exceeds 1999.
Adjust the applied pressure
Out of pressure display range (Lower limit)
within the rated pressure.
Ⅺ
FFF
A pressure less than –10% FS of pressure
range is applied, or when indicated value
falls below –1999.
Ⅺ
E-0
During zero point adjustment, applied
Open the unit to the atmos-
pressure is outside the range of ±10% FS
phere and perform zero
point adjustment again.