Controls and indicators – Notifier RP-2002C User Manual
Page 2

Page 2 of 4 — Canadian DN-60444:B1 • 12/22/11
PROGRAMMING AND SOFTWARE:
• Custom English labels (per point) may be manually entered
or selected from an internal library file.
• Programmable Abort operation.
• Three programmable Form-C relay outputs.
• Pre-programmed and custom application templates.
• Continuous fire protection during online programming at the
front panel.
• Program Check automatically catches common errors not
linked to any zone or input point.
USER INTERFACE:
• Integral 80-character LCD display with backlighting.
• Real-time clock/calendar with automatic daylight savings
adjustments.
• ANN-Bus for connection to annunciators.
• Audible or silent walk test capabilities.
• Piezo sounder for alarm, trouble, and supervisory.
Controls and Indicators
LED INDICATORS
• FIRE ALARM (red).
• SUPERVISORY (yellow).
• TROUBLE (yellow).
• AC POWER (green).
• ALARM SILENCED (yellow).
• DISCHARGED (red).
• PRE-DISCHARGE (red indicator).
• ABORT (yellow indicator).
CONTROL BUTTONS
• ACKNOWLEDGE.
• ALARM SILENCE.
• SYSTEM RESET (lamp test).
• DRILL.
AC Power – TB1
•
RP-2002C: 120 VAC, 60 Hz, 3.66 amps.
•
Wire size: minimum #14 AWG (2.0 mm
2
) with 600V insula-
tion.
• Supervised, nonpower-limited.
Battery (sealed lead acid only) – J12:
•
Maximum Charging Circuit - Normal Flat Charge: 27.6
VDC @ 1.4 amp. Supervised, nonpower-limited.
•
Maximum Charger Capacity: 18 Amp Hour battery (two
18 Amp Hour batteries can be housed in the FACP cabinet.
Larger batteries require separate battery box such as the
BB-26 or NFS-LBBR).
•
Minimum Battery Size: 12 Amp Hour.
Initiating Device Circuits - TB4 and TB6
• Zones 1 - 5 on TB4.
• Zone 6 on TB6.
• Supervised and power-limited circuitry.
• Style B (Class B) wiring with Style D (Class A) option.
• Normal Operating Voltage: Nominal 20 VDC.
• Alarm Current: 15 mA minimum.
• Short Circuit Current: 40 mA max.
• Maximum Loop Resistance: 100 Ohms.
• End-of-Line Resistor: 4.7K Ohms, 1/2 watt (PN 71252).
• Standby Current: 4 mA.
Refer to the Notifier Device Compatibility Document for listed
compatible devices.
Notification Appliance and Releasing Circuit(s) - TB5 and
TB7
• Four Output Circuits.
• Style Y (Class B) or Style Z (Class A) with optional con-
verter module.
• Special Application power.
• Supervised and power-limited circuitry.
• Normal Operating Voltage: Nominal 24 VDC.
• Maximum Signaling Current: 7.0 amps (3.0 amps maximum
per NAC).
• End-of-Line Resistor: 4.7K Ohms, 1/2 watt (PN 71252).
• Max. Wiring Voltage Drop: 2 VDC.
Refer to the Notifier Device Compatibility Document for com-
patible listed devices.
Form-C Relays - Programmable - TB8
• Relay 1 (factory default programmed as Alarm Relay)
• Relay 2 (factory default programmed as fail-safe Trouble
Relay)
• Relay 3 (factory default programmed as Supervisory Relay)
• Relay Contact Ratings:
– 2 amps @ 30 VDC (resistive)
– 0.5 amps @ 30 VAC (resistive)
Auxiliary Trouble Input – J6
The Auxiliary Trouble Input is an open collector circuit which
can be used to monitor external devices for trouble conditions.
It can be connected to the trouble bus of a peripheral, such as
a power supply, which is compatible with open collector cir-
cuits.
Special Application Resettable Power - TB9
•
Operating Voltage: Nominal 24 VDC.
•
Maximum Available Current: 500 mA - appropriate for
powering 4-wire smoke detectors (see note).
• Power-limited Circuitry.
Refer to the Notifier Device Compatibility Document for com-
patible listed devices.
NOTE: Total current for resettable power, nonresettable power and
Output Circuits must not exceed 7.0 amps.
Special Application Resettable or Nonresettable Power -
TB9
•
Operating Voltage: Nominal 24 VDC.
•
Maximum Available Current: 500 mA (see note 1).
• Power-limited Circuitry.
• Jumper selectable by JP31 for resettable or nonresettable
power.
Refer to the Notifier Device Compatibility Document for com-
patible listed devices.