Notifier BEAM1224(S) User Manual
Conventional beam smoke detectors, General, Features
DN-6975:B • 08/26/2009 — Page 1 of 2
BEAM1224(A) and
BEAM1224S(A)
Conventional Beam Smoke Detectors
Conventional Initiating Devices
DN-6975:B • I-405
General
The System Sensor BEAM1224 and BEAM1224S are four-
wire conventional reflected beam smoke detectors. They are
uniquely suited for protecting open areas with high ceilings
where spot-type smoke detectors are difficult to install and
maintain. BEAM1224 and BEAM1224S are to be used with UL
Listed compatible fire alarm control panels only. Installation of
the single-ended reflective design is much quicker than a dual-
ended projected beam detector. Alignment is easily accom-
plished with an optical sight and a two-digit signal strength
meter incorporated into the beam detector. Listed for operation
from –22°F to 131°F, the BEAM1224 and BEAM1224S can be
used in open-area applications to provide early warning in
environments where temperature extremes exceed the design
limits for other types of smoke detection.
The BEAM1224 and BEAM1224S are a transmitter/receiver
unit and a reflector. When smoke enters the area between the
unit and the reflector, it causes a reduction in the signal
strength. When the smoke level (signal strength) reaches the
predetermined threshold, an alarm is activated. The detectors
have four standard sensitivity selections as well as two Accli-
mate® settings. When either Acclimate® setting is selected,
the detector will automatically adjust its sensitivity using
advanced software algorithms to select the optimum sensitivity
for the specific environment.
The BEAM1224S has an integral sensitivity test feature of a fil-
ter attached to a servomotor inside the detector optics. Activa-
tion of the RTS151 or RTS151KEY remote test station moves
the filter into the pathway of the light beam, testing the detec-
tor’s sensitivity. This sensitivity test feature allows the user to
quickly and easily meet the annual maintenance and test
requirements of NFPA 72, without physical access to the
detector.
NOTE: Unless otherwise specified, the term BEAM1224 is used in
this data sheet to refer to both the BEAM1224 and the
BEAM1224A (ULC-listed version). Likewise, BEAM1224S
includes BEAM1224SA.
Features
•
Transmitter/receiver built into same unit.
•
Six user-selectable sensitivity levels.
•
16' to 328' (use BEAMLRK beyond 230') protection range.
•
Removable plug-in terminal blocks.
•
Digital display for easy alignment.
•
Built-in automatic gain control compensates for signal dete-
rioration from dust buildup.
•
Paintable cover.
•
Optional remote test station.
•
Optional long-range kit (BEAMLRK) for applications in
excess of 230' (70 m).
•
Optional multi-mount kit (BEAMMMK) providing ceiling or
wall mount capability with increased angular adjustment.
•
Optional heater kits (BEAMHK and BEAMHKR) for preven-
tion of condensation (not intended to increase or reduce the
specified operating temperature).
•
Optional heavy-duty mounting bracket (6500-MMK)
Specifications
OPERATIONAL SPECIFICATIONS
Protection range: 16 to 230 feet (5 to 70 m), 230 to 328 feet
(70 to 100 m) using optional BEAMLRK kit.
Adjustment angle: ±10° horizontal and vertical. Note that the
optics move independently of the unit.
Sensitivity (6 levels):
•
Level 1 — 25%.
•
Level 2 — 30%.
•
Level 3 — 40%.
•
Level 4 — 50%.
•
Acclimate® Level 5 — 30% to 50%.
•
Acclimate® Level 6 — 40% to 50%.
Fault condition (trouble):
•
96% or more obscuration blockage.
•
In alignment mode.
•
Improper initial alignment.
•
Self-compensation limit reached.
Alignment aid:
•
Optical gunsight.
•
Integral signal strength indication.
•
Two-digit display.
Indicators:
•
Alarm — local red LED and remote alarm.
•
Trouble — local yellow LED and remote trouble.
•
Normal — local flashing green LED.
Test/reset features:
Integral sensitivity test filter (BEAM1224S only, requires exter-
nal power supply).
•
Sensitivity filter (incremental scale on reflector).
BEAM1224(A)
with BEAMMMK
(sold separately)
BEAM1224(A)
with Reflective Plate
6975beammk.jpg