DN-6931:A1 • 2/9/10 — Page 1 of 2

5600 Series

Mechanical Heat Detectors

Conventional Initiating Devices

DN-6931:A1 • I-304

GENERAL

System Sensor’s 5600 Series mechanical heat detectors offer

property protection against fire and for non-life-safety installa-

tions, where smoke detectors are inappropriate.
Multiple configurations. The 5600 Series offers a full line of

configurations to accommodate a broad range of applications.

Both single- and dual-circuit models are offered, each avail-

able for low- and high-temperature ratings with either fixed-

temperature or combination fixed-temperature/rate-of-rise

(ROR) activation. The ROR element of the fixed/ROR models

is restorable, to accommodate field-testing the unit.
Installation flexibility. To satisfy a variety of installations, the

5600 Series easily mounts to single-gang and octagonal back-

boxes. These models also accommodate 4" (101.6 mm)

square backboxes when used with a plaster ring. The mount-

ing bracket is reversible to allow for flush- and surface-mount

backbox installations.
Visual identification. The 5600 Series provides clear mark-

ings on the exterior of the unit to ensure that the proper detec-

tor is being used. Alphanumeric characters identify the

activation method, as well as the temperature rating, in

degrees Fahrenheit and Celsius. Fixed temperature models

are identified “FX”, while combination fixed/rate-of-rise units

are marked “FX/ROR”. The 5600 Series also provides a col-

lector as a post-activation indicator. Once the detector has

been activated, the collector drops from the unit to allow easy

identification of the specific unit in alarm.

FEATURES

• Multiple configurations available:

– Fixed-temperature (non-resettable) or combination fixed

(non-resettable)/rate-of-rise (self-restoring).

– Low-temperature and high-temperature ratings.
– Single-circuit and dual-circuit.

• Easy-to-read alphanumeric identification of detector type

and temperature rating.

• External collector provides visual indication of activation.
• Reversible mounting bracket for flush- and surface-mount

installations.

• Flexible mounting capabilities: single-gang, 3.5" or 4" octag-

onal, 4" (101.6 mm) square with plaster ring.

• Easy-to-use terminal screws provide a more positive wiring

connection.

• Low-profile design to coordinate with room aesthetics.

AGENCY LISTINGS AND APPROVALS

These listings and approvals apply to the modules specified in

this document. In some cases, certain modules or applications

may not be listed by certain approval agencies, or listing may

be in process. Consult factory for latest listing status.

UL Listed: S2101

ULC Listed: S2101 (all with “A” suffix)

MEA: 199-03-E

CSFM: 7270-1209:227, 7270-1653:167

• FM Approved

SPECIFICATIONS

PHYSICAL SPECIFICATIONS

Maximum installation temperature:

For models 5601P, 5603, 5621, 5623: 100°F (38°C).
For models 5602, 5604, 5622, 5624: 150°F (65.6°C).

Alarm temperature:

For models 5601P, 5603, 5621, 5623: 135°F (57°C).
For models 5602, 5604, 5622, 5624: 194°F (90°C).

Rate-of-Rise Threshold:

15°F (8.3°C) per minute (models

5601, 5602, 5621, 5622 only).

Operating Humidity Range:

5% to 95% RH noncondensing.

Input Terminals:

non-polarized, accept 14 to 22 AWG (2.0 to

0.33 mm²).

Dimensions:

diameter with mounting bracket: 4.57" (116 mm);

height with mounting bracket: 1.69" (43 mm).

Weight:

6 oz. (170 grams).

Mounting Options:

3.5" (88.9 mm) octagonal backbox; 4"

(101.6 mm) octagonal backbox; single-gang backbox; 4"

(101.6 mm) square backbox with a square-to-round plaster

ring.

ELECTRICAL SPECIFICATIONS

Mechanical heat detector shall be a System Sensor 5600

Series model number ______, Listed to Underwriters Labora-

tories UL 521 for Heat Detectors for Fire Protective Signaling

Systems. The detector shall be either a single-circuit or a dual-

circuit type, normally open. The detector shall be rated for acti-

vation at either 135°F (57°C) or 194°F (90°C), and shall acti-

vate by means of a fixed-temperature thermal sensor, or a

combination fixed-temperature/rate-of-rise thermal sensor.

The rate-of-rise element shall be activated by a rapid rise in

temperature, approximately 15°F (8.3°C) per minute. The

detector shall include a reversible mounting bracket for mount-

Operating Voltage

Contact Ratings (resistive)

6 - 125 VAC

3.0 A

6 - 28 VDC

1.0 A

125 VDC

0.3 A

250 VDC

0.1 A