System specifications, System capacity, Electrical specifications – Notifier RP-2002C User Manual
Page 4: Cabinet specifications, Shipping specifications, Temperature and humidity ranges, Nfpa standards, Agency listings and approvals

System Capacity
• Annunciators ..................................................... .................2
Electrical Specifications
•
RP-2002C: (FLPS-7 Power Supply): 120 VAC, 60 Hz, 3.66
amps
•
Wire size: minimum 14 AWG (2.0 mm²) with 600 V insula-
tion, supervised, nonpower-limited
Cabinet Specifications
Door: 48.92 cm. high x 42.73 cm. wide x 1.82 cm. deep. Back-
box: 48.26 cm. high x 42.29 cm. wide x 13.34 cm. deep. Trim
Ring (TR- CE): 55.88 cm. high x 49.91 cm. wide.
Shipping Specifications
Dimensions:
– Height 50.80cm
– Width 57.15cm
– Depth 21.59cm
Temperature and Humidity Ranges
This system meets NFPA requirements for operation at 0 –
49°C and at a relative humidity 93% ± 2% RH (noncondens-
ing) at 32°C ± 2°C. However, the useful life of the system's
standby batteries and the electronic components may be
adversely affected by extreme temperature ranges and humid-
ity. Therefore, it is recommended that this system and its
peripherals be installed in an environment with a normal room
temperature of 15 – 27°C.
NFPA Standards
The RP-2002C complies with the following NFPA 72 Fire
Alarm Systems requirements:
– NFPA 12 CO
2
Extinguishing Systems
– NFPA 12A Halon 1301 Extinguishing Systems
– NFPA 12B Halon 1211 Extinguishing Systems
– NFPA 72 National Fire Alarm Code for Local Fire Alarm
Systems and Remote Station Fire Alarm Systems
(requires an optional Remote Station Output Module)
– NFPA 2001 Clean Agent Fire Extinguishing Systems
Agency Listings and Approvals
The listings and approvals below apply to the basic RP-2002C
control panel. In some cases, certain modules may not be
listed by certain approval agencies, or listing may be in pro-
cess. Consult factory for latest listing status.
•
ULC: S635
•
Seismic Listing: Reference certificiate of compliance
VMA - 45894-01 by the VMC Group
©2011 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
Page 4 of 4 — Canadian DN-60444:B1 • 12/22/11
This document is not intended to be used for
installation purposes. We try to keep our prod-
uct information up-to-date and accurate. We
cannot cover all specific applications or anticipate
all requirements. All specifications are subject to
change without notice.
For more information, contact Notifier.
(888) 289-1114
10 Whitmore Road
Woodbridge, Ontario L4L 7Z4
www.notifier.com
SYSTEM SPECIFICATIONS