beautypg.com

Notifier N100-ISO User Manual

N100-iso(a), Fault isolator module for firewarden series panels, General

background image

DN-6994:B • 01/05/2012 — Page 1 of 2

N100-ISO(A)

Fault Isolator Module
for FireWarden Series Panels

Addressable

DN-6994:B • A1-370

General

The

NOTIFIER N100-ISO(A) Fault Isolator Module is used

with

FireWarden Series panels to protect the system against

wire-to-wire short circuits on the SLC loop. The N100-ISO(A)

should be placed between each device on the SLC loop to iso-

late a short-circuit problem between the modules. It is required

for true Style 7 operation so that other devices can continue to

operate normally in the event of a short-circuit on the SLC.

Features

• Powered by SLC loop directly, no external power required.
• Mounts in standard junction boxes (4.0"/10.16 cm square,

2.125"/5.398 cm deep).

• Integral LED blinks to indicate normal condition. Illuminates

steady when short circuit condition is detected.

• High noise (EMF/RFI) immunity.

Applications

The Fault Isolator Modules should be spaced between groups

of sensors in a loop to protect the rest of the loop. Use to iso-

late short circuit problems within a section of a loop so that

other sections can continue to operate normally. The N100-

ISO(A) supports a maximum of 25 devices in-between isola-

tors, except when using relay bases.

NOTE: LOADS PER RELAY BASE AND ISOLATORS/ISOLATOR
BASES: The maximum number of addressable devices between
isolators (or B224BIA isolator bases) is 25 devices.

B224RB relay bases draw more current than other intelligent
devices. When calculating the 25-device maximum, B224RB rep-
resents 2.5 DEVICES; see example on page 2.

NOTE: ON MAXIMUM NUMBER OF DEVICES: See the

SLC

Manual (52304) for information on loss of addresses due to current
limitations. Each module or base added reduces the capacity of
address positions in an

SLC. All SLC field devices must have been

purchased after February 1995 to meet the aforementioned
requirements. If the

SLC field devices were purchased prior to

February 1995, each isolator used reduces the capacity of an

SLC

by two address positions. Requirements differ as applied to relay
bases; see note above.

Specifications

Operating voltage: 15 – 32 VDC (peak).

Maximum current upon activation due to short circuit:
refer to the manual for the main FACP.

Standby current: 450 μA maximum; N100-ISO(A) is not

isolating – relay closed.

Temperature range: 32°F to 120°F (0°C to 49°C).

Relative humidity: 10% to 93%.

Weight: 5 oz. (150 grams).

Dimensions: 4.5”H x 4.5”W x 0.25” D (11.43 cm H x

11.43 cm W x 0.635 cm D).

Construction

The face plate is made of off-white plastic. Module includes

yellow LED indicator that pulses when normal and illuminates

steady when a short is detected.

Operation

Automatically opens circuit when the line voltage drops below

four volts. Fault Isolator Modules should be spaced between

groups of addressable devices (maximum 25, see notes on
page 1

) in a loop to protect the rest of the loop. If a short

occurs between any two isolators, then both isolators immedi-

ately switch to an open circuit state and isolate the groups of

sensors between them. The remaining units on the loop con-

tinue to fully operate.
In Style 4 loops, the N100-ISO(A) is generally used at each T-

tap branch, to limit the effect of short circuits on a branch to the

devices on that branch. The LED indicator is on continuously

during a short circuit condition.
The N100-ISO(A) Fault Isolator Module automatically restores

the shorted portion of the communications loop to normal.

Installation

• Mount on a standard junction box (4.0"/10.16 cm square)

which is at least 2.125"/5.398 cm deep.

• Terminal screws are provided for “in and out” wiring.
• Installation instructions are provided with each module.
• Surface-mount box is available as an option.

2243devices.wmf

isolator
module

or base

isolator
module

or base

detector

module

25 DEVICES

N100-ISO(A)