GENERAL
Wheelock’s patented 2-wire AS Series Audible Strobe Applicances
and AH Series Audible Devices offer more features with low
current draw.
Strobe options for wall mount models include 1575cd or Wheelock’s
patented MCW multi-candela wall strobes with field selectrable
candela settings of 15/30/75/110cd.
Ceiling mount models incorporate Wheelock’s patented MCC multi-
candela ceiling strobe with field selectrable intensities of 15/30/75/
95cd.
The audible provides a selectable choice of either a continous horn
or temporal pattern (Code 3) when constant voltage from a Fire
Alarm Panel (FACP) is applied. Each tone has 3 dBA settings to
choose from.
When used with the Wheelock Series SM or DSM Sync Module or
with a power supply with the Wheelock sync protocol,
synchronization of the continous horn tone provides the temporal
(code 3) tone (mandated by NFPA 72) simultaneously for all audible
appliances. This ensurses a distrinct temporal (code 3) pattern
when 2 or more audibles are within hearing distance. If not
synchronized the temporal sound could overlap and not be
distrinctive. At the same time the strobes will be synchronized.
This provides the ability to comply with ADA guidelines concerning
photosensitive epilepsy and the NFPA standards when installing
2 or more visual appliances within the field of view all of this puls
the ability to silence the audible is achieved by using only 2 wire.
FEATURES
• ADA/NFPA/UFC/ANSI Compliant
• AS Series Audible Strobe Devices are available in wall
and ceiling-mount models:
Wall mount models offered are available with Field Selectrable
Candela Settings of 15/30/75/110cd or 1575cd (single candela
model)
Ceiling mount models offered are available with field
selectrable candela settings of 15/30/75/95cd
• Selectable Continous Horn or Temporal (Code 3)
• 3 Selectrable dBA settings (99, 95 abd 90 dBA) in both tones
• Patented 2-Wire Audible Strobe Appliance
• Patented Universal Mounting Plate
• Weatherproof models are available for outdoor use
• Strobes produce 1 flash per second over the regulated voltage
range
• 12 and 24 VDC models with wide UL “Regulated Voltage Range”
using filtered DC or unfiltered FWR input voltage
• Synchronize with Wheelock SM, DSM or power supply with
built-in Wheelock sync protocol
• Fast installation with IN/OUT screw terminals using #12 and #18
AWG wires
E 5946
MEA
151-92-E
7125-0785:131
CS 356
DN-5566 • J-122
March 30, 2004
Section: Audio/Visual Devices
Wheelock
AS Series Audible Strobe Devices
and AH Series Audible Devices
California
State Fire
Marshal
GENERAL NOTES
• Strobes are designed to flash at 1 flash per second minimum
over the Regulated Voltage Range. Note that NFPA-72 (1999)
specifies a flash rate of 1 to 2 flashes per second and ADA
Guildelines specify a flash rate of 1 to 3 flashes per second.
• All candela ratings represent minimum effective Strobe intensity
based on UL Standard 1971.
• AS Series Strobe products are listed under UL Standard 1971for
indoor use with a temperature range of 32° F to 120° F (O° C to
49° C) and maximum humidity of 93% (+ 2%)
• AH-24 Series horns are listed under UL Standard 464 for audible
signal appliances (indoor use only).
• AH-24WP Series audible appliances are listed under UL Stan-
dard 464 for indoor/outdoor use with a temperature range of -
31° F to 150° F (-35° C to 66° C) and maximum humidity of 95%.
• “Regulated Voltage Range” is the newest terminology
used by UL to identify the voltage range. Prior this
change, UL used the terminology “Listed Voltage Range”.
AS Audible Strobe
AH Audible
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications
or anticipate all requirements. All specifications are subject to change without notice.
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
12 Clintonville Road, Northford, Connecticut 06472
NOTIFIER® is a Honeywell company.