Hydraulic generator controller – hgc-2 – High Country Tek HGC-2, Closed Loop Controller User Manual
Page 21
Hydraulic Generator Controller – HGC-2
21
HGC-2 Error code Description (STATUS)
:
IMPORTANT NOTES:-
• ALWAYS Mount HGC-2 controller with I/O connector facing downwards to avoid debris collection.
• Recommended tightening torques for securing bolts on the HGC-2 module are as follows:-
For 2 x #6 (4mm) bolts - Dry Torque = 6 Ft-Lbs - Lubricated Torque = 4 Ft-Lbs
Label
Inches
Millimeters
A
3.0
76.2
B
2.0
50.8
C
0.25
6.4
D
1.0
25.4
E
0.188
4.80
HGC-2 Hardware Description
:
Blink
Definition
OFF
System is OK and operating normally
2
Open Circuit On Controller Output
– wires to solenoid disconnected while under power
3
Short Circuit On Controller Output - wires or solenoid have become short circuited
5
Frequency Fault
– output frequency has been below min. or above max. for greater than fault time
Note:-
• The ‘STATUS’ led is a monitor is used to indicate locally the controller operation only
• NO external output is provided to mimic the STATUS led