For alarm state condition – Red Lion ITMS User Manual
Page 13
13
ALARM 1 (40018) & 2 (40014) ACTION REGISTER TABLE
INPUT TYPE REGISTER (40008) TABLE
SENSOR FAILURE ACTION REGISTER (40022) TABLE
FOR ALARM STATE CONDITION
USER INPUT ACTION REGISTER (40013) TABLE
Examples:
Alarm 1 (40018):
Stand-by off, Latch on = 0 0 0 1 <1 >
Absolute Lo, Balanced = 0 0 1 0 < 2>
<1 2>
Alarm 2 (40014):
Stand-by on, Latch off = 0 0 1 0 <2 >
Band Outside = 0 1 1 1 < 7>
<27>
COMMUNICATIONS REGISTER (40026) AND COILS 1-8 TABLE
* When reading register 40026, B7 will be a 0. When writing (changing ITMS communications to the new setting), change B7 to a 1.
Mode
Parity
Baud
Coil 8
B7*
Coil 7
B6
Coil 6
B5
Coil 5
B4
Coil 4
B3
Coil 3
B2
Coil 2
B1
Coil 1
B0
Coil 8 =0
HEX
Coil 8 =1
HEX
RTU
8N1,2
300
0 / 1
0
1
0
0
0
0
0
<20>
RTU
8N1,2
600
0 / 1
0
1
0
0
0
0
1
<21>
RTU
8N1,2
1200
0 / 1
0
1
0
0
0
1
0
<22>
RTU
8N1,2
2400
0 / 1
0
1
0
0
0
1
1
<23>
RTU
8N1,2
4800
0 / 1
0
1
0
0
1
0
0
<24>
RTU
8N1,2
9600
0 / 1
0
1
0
0
1
0
1
<25>
RTU
8N1,2
19200
0 / 1
0
1
0
0
1
1
0
<26>
RTU
8N1,2
38400
0 / 1
0
1
0
0
1
1
1
<27>
RTU
8E1
300
0 / 1
0
1
0
1
0
0
0
<28>
RTU
8E1
600
0 / 1
0
1
0
1
0
0
1
<29>
RTU
8E1
1200
0 / 1
0
1
0
1
0
1
0
<2A>
RTU
8E1
2400
0 / 1
0
1
0
1
0
1
1
<2B>
RTU
8E1
4800
0 / 1
0
1
0
1
1
0
0
<2C>
RTU
8E1
9600
0 / 1
0
1
0
1
1
0
1
<2D>
RTU
8E1
19200
0 / 1
0
1
0
1
1
1
0
<2E>
RTU
8E1
38400
0 / 1
0
1
0
1
1
1
1
<2F>
RTU
8O1
300
0 / 1
0
1
1
1
0
0
0
<38>
RTU
8O1
600
0 / 1
0
1
1
1
0
0
1
<39>
RTU
8O1
1200
0 / 1
0
1
1
1
0
1
0
<3A>
RTU
8O1
2400
0 / 1
0
1
1
1
0
1
1
<3B>
RTU
8O1
4800
0 / 1
0
1
1
1
1
0
0
<3C>
RTU
8O1
9600
0 / 1
0
1
1
1
1
0
1
<3D>
RTU
8O1
19200
0 / 1
0
1
1
1
1
1
0
<3E>
RTU
8O1
38400
0 / 1
0
1
1
1
1
1
1
<3F>
Latched
Off=Auto
2nd Nibble
HEX
Stand By
B7
B6
B5
off
off
0
0
0
0
<0 >
off
on
0
0
0
1
<1 >
on
off
0
0
1
0
<2 >
on
on
0
0
1
1
<3 >
B4
< 8>
< 7>
0
1
0
1
0
1
1
0
2
2
8
7
Band Inside
Band Outside
< 6>
0
1
1
0
2
6
Deviation Lo
< 5>
1
0
1
0
2
5
Deviation Hi
< 4>
0
0
1
0
2
1
4
Absolute Lo, unbalanced
< 3>
1
1
0
0
2
1
3
Absolute Hi, unbalanced
< 2>
0
1
0
0
2
1
2
Absolute Lo, balanced
< 1>
1
0
0
0
2
1
1
Absolute Hi, balanced
< 0>
0
0
0
0
2
1
0
Manual
1st Nibble
HEX
B0
B1
B2
B3
ALARMS
MODE
ACTION
See Setpoint Alarm Figures, Page 5, for illustrations of alarm operation.
MODE
TYPE
MODE
TYPE
MODE
TYPE
0
Tc - T
5
Tc - S
10
RTD - 385
1
Tc - E
6
Tc - B
11
RTD - 392
2
Tc - J
7
Tc - N
12
RTD - 672
3
Tc - K
8
Tc - C
13
LIN Ohms
4
Tc - R
9
LIN mV
MODE
ACTION
ALARM
INPUT ACTIVATION
<0000>
Reset
1
Level (Maintained)
<0001>
Reset
2
Level (Maintained)
<0002>
Reset
1 & 2
Level (Maintained)
<0003>
Set
1
Level (Maintained)
<0004>
Set
2
Level (Maintained)
<0005
Set
1 & 2
Level (Maintained)
<0010>
Reset
1
Edge (Momentary)
<0011>
Reset
2
Edge (Momentary)
<0012>
Reset
1 & 2
Edge (Momentary)
<0013>
Set
1
Edge (Momentary)
<0014>
Set
2
Edge (Momentary)
<0015>
Set
1 & 2
Edge (Momentary)
MODE
ALARM 1
ALARM 2
0
Off
Off
1
On
On
2
Off
On
3
On
Off